Toshiba MMY-MAP1006FT8(J)P-E Service Manual page 176

Super heat recovery multi-e (multi type) outdoor unit
Hide thumbs Also See for MMY-MAP1006FT8(J)P-E:
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
Sub-code
controller
code
Detected outdoor unit No.
P19
P19
P20
P20
Location
of
Description
System status
detection
I/F
4-way valve
All stop
reversing
trouble
I/F
Activation of
All stop
high-pressure
protection
− 175 −
Check code detection
Check items (locations)
condition(s)
Abnormal refrigerating cycle
• Check for trouble in main
data is collected during
body of 4-way valve.
heating operation.
Check for coil trouble in
4-way valve and loose
connection of its
connector.
Check resistance
characteristics of TS1
and TE1,TE2 sensors.
• Check output voltage
characteristics of P and
Ps pressure sensors.
• Check for wiring trouble
involving TE1 and TL1
sensors.
• Check for trouble in PD
<During cooling operation>
PD sensor detects pressure
pressure sensor.
equal to or greater than
• Check service valves (gas
3.85 MPa.
side, liquid side) to confirm
<During heating operation>
full opening.
PD sensor detects pressure
• Check for trouble in
outdoor fan.
equal to or greater than 3.6
MPa.
• Check for trouble in
outdoor fan motor.
• Check outdoor PMV
(PMV1, 4) for clogging.
• Check indoor/outdoor heat
exchangers for clogging.
• Check for short-circuiting
of outdoor suction/
discharge air flows.
• Check SV2 circuit for
clogging.
• Check for trouble in outdoor
P.C. board (I/F).
• Check for trouble in indoor
fan system (possible cause
of air flow reduction).
• Check opening status of
indoor PMV.
• Check indoor-outdoor
communication line for
wiring trouble.
• Check for trouble operation
of check valve in discharge
pipe convergent section.
• Check gas balancing SV4
valve circuit.
• Check SV5 valve circuit.
• Check for refrigerant
overcharging.