Toshiba MMY-MAP1006FT8(J)P-E Service Manual page 161

Super heat recovery multi-e (multi type) outdoor unit
Hide thumbs Also See for MMY-MAP1006FT8(J)P-E:
Table of Contents

Advertisement

Using indoor unit indicators (receiving unit light block) (wireless type)
To identify the check code, check the 7-segment display on the header unit. To check for check codes not
displayed on the 7-segment display, consult the "List of Check Codes (Indoor Unit)" in "8-2. Troubleshooting
Method".
L
g i
t h
b
o l
c
k
C
h
Operation Timer
Ready
All lights out
Operation Timer
Ready
Blinking
Operation Timer
Ready
Blinking
Operation Timer
Ready
Alternate blinking
Operation Timer
Ready
Alternate blinking
e
c
k
c
o
d
e
Power turned off or trouble in wiring between receiving and indoor units
E01
Troubled reception
E02
Troubled transmission
E03
Loss of communication
E08
Duplicated indoor unit No. (address)
E09
Duplicated master remote controller
E10
Indoor unit inter-MCU communication trouble
E12
Automatic address starting trouble
E17
Communication trouble between indoor unit(s) and FS unit(s)
E18
Trouble or poor contact in wiring between indoor units, indoor power turned off
Trouble or poor contact in wiring between indoor and outdoor
E04
units (loss of indoor-outdoor communication)
E06
Troubled reception in indoor-outdoor communication (Signal lack of indoor unit)
E07
Troubled transmission in indoor-outdoor communication
E15
Indoor unit not found during automatic address setting
E16
Too many indoor units connected/overloading
E19
Trouble in number of outdoor header units
E20
Detection of refrigerant piping communication trouble during automatic address setting
E23
Troubled transmission in outdoor-outdoor communication
E25
Duplicated follower outdoor address
E26
Troubled reception in outdoor-outdoor communication, Signal lack of outdoor unit
E28
Outdoor follower unit trouble
E31
IPDU communication trouble, sub MCU communication trouble
P01
Indoor AC fan trouble
P10
Indoor overflow trouble
P12
Indoor DC fan trouble
P13
Outdoor liquid backflow detection trouble
P03
Outdoor discharge (TD1) temperature trouble
P04
Activation of outdoor high-pressure SW
Open phase/power failure
P05
Inverter DC voltage (Vdc) trouble
MG-CTT trouble
P07
Outdoor heat sink overheating trouble - Poor cooling of electrical component (IPM) of outdoor unit
P15
Gas leak detection - insufficient refrigerant charging
P17
Outdoor discharge (TD2) temperature trouble
P19
Outdoor 4-way valve reversing trouble
P20
Activation of high-pressure protection
P22
Outdoor fan IPDU trouble
P26
Outdoor IPM short-circuit trouble
P29
Compressor position detection circuit trouble
P31
Shutdown of other indoor unit in group due to fault (group follower unit trouble)
: Goes off
: Lighting
Cause of check code
Receiving unit
− 160 −
: Blinking (0.5 seconds)
Trouble or poor contact in
wiring between receiving
and indoor units
Setting trouble
MG-CTT: Magnet contactor