Whirlpool W10196159C Installation Instructions Manual page 4

30" (76.0cm) freestanding electric ranges
Table of Contents

Advertisement

Available languages

Available languages

Cabinet
Dimensions
Cabinet opening dimensions shown are for 25" (64.0 cm)
countertop depth, 24" (61.0 cm) base cabinet depth and
36" (91.4 cm) countertop height.
IMPORTANT:
If installing a range hood or microwave hood
combination
above the range, follow the range hood or
microwave hood combination
installation instructions
for
dimensional clearances above the cooktop surface.
A freestanding
range may be installed next to combustible
walls
with zero clearance.
\
\
E
A. 13" (33.0 cm) max. upper cabinet depth
B. 30" (76.2 cm) min. opening width
C. For minimum clearance to top of cooktop,
see NQTE*
D. 31" (78.7 cm) min. opening width
E. Outlet - 8" (20.3 cm) to 22" (55.9 cm) from either cabinet,
7" (17. 8 cm) max. from floor.
F. _" (2.2 cm) min. required between cutout and cabinet door or
hinge.
*NOTE: 24" (61.0 cm) minimum when bottom of wood or metal
cabinet is covered by not less than 1/4"(0.64 cm) flame retardant
millboard covered with not less than No. 28 MSG sheet steel,
0.015" (0.4 mm) stainless steel, 0.024" (0.6 mm) aluminum or
0.020" (0.5 mm) copper.
30" (76.2 cm) minimum clearance between the top of the
cooking platform and the bottom of an uncovered wood or metal
cabinet.
Electrical Shock Hazard
Electrically ground range.
Failure to do so can result in death, fire, or
electrical
shock.
If codes permit and a separate ground wire is used, it is
recommended
that a qualified electrical installer determine that
the ground path is adequate and wire gauge are in accordance
with local codes.
Be sure that the electrical connection and wire size are adequate
and in conformance
with CSA Standard C22.1, Canadian
Electrical Code, Part 1 - latest edition, and all local codes and
ordinances.
A copy of the above code standards can be obtained from:
Canadian Standards Association
178 Rexdale Blvd.
Toronto, ON M9W 1R3 CANADA
Check with a qualified electrical installer if you are not sure
the range is properly grounded.
Range Rating*
Rating of
Circuit
Power
Protection
Supply Cord
120/240 Volts
120/208 Volts
Amps
Amps
8.8 - 16.5 KW
7.8 - 12.5 KW
40
40 or 50
16.6-22.5KW
12.6-18.5KW
50
50
*The NEC calculated load is less than the total connected
load
listed on the model/serial
rating plate.
A time-delay fuse or circuit breaker is recommended.
This range is equipped with a CSA International Certified
Power Cord intended to be plugged into a standard 14-50R
wall receptacle. Be sure the wall receptacle is within reach of
range's final location.
Do not use an extension cord.