6 Set up with the display and adjustment module
Selection of national
language
Main menu
36
This menu item is used to select the national language for further pa-
rameter adjustment. You can change the selection via the menu item
"Setup - Display, Menu language".
With the "OK" key you move to the main menu.
6.4

Parameter adjustment - Quick setup

To quickly and easily adapt the sensor to the application, select
the menu item "Quick setup" in the start graphic on the display and
adjustment module.
Select the individual steps with the [->] key.
After the last step, "Quick setup terminated successfully" is displayed
briefly.
Information:
The echo curve of setup is stored automatically during the quick
setup.
The return to the measured value indication is carried out through the
[->] or [ESC] keys or automatically after 3 s
You can find "Extended adjustment" in the next sub-chapter.
6.5

Parameter adjustment - Extended adjustment

The main menu is divided into five sections with the following func-
tions:
Setup: Settings, e.g., for measurement loop name, units, application,
adjustment, signal output
Display: Settings, e.g., for language, measured value display, lighting
Diagnosis: Information, for example, on device status, peak value,
simulation, echo curve
Additional adjustments: Date/Time, reset, copy function, scaling,
current output, false signal suppression, linearization, HART mode,
special parameters
Info: Instrument name, hardware and software version, calibration
date, instrument features
In the main menu item "Setup", the individual submenu items
should be selected one after the other and provided with the correct
VEGAPULS 64 • 4 ... 20 mA/HART - two-wire