Installation Instructions; Boiler Ratings And Capacities - Dunkirk XEB-2 Installation, Operation & Maintenance Manual

Gas-fired hot water induced draft boiler
Table of Contents

Advertisement

This boiler cannot be used with all types of chimneys. Read
these instructions carefully before installing.
These Gas-Fired Hot Water Boilers are low pressure, sec-
tional cast iron boilers Design Certified by C.S.A. (Canadian
Standards Association) for use with Natural and Propane
Gases. They are constructed and hydrostatically tested for
a maximum working pressure of 50 psi in accordance with
A.S.M.E. Boiler and Pressure Vessel Code Section IV Stan-
dards for cast iron heating boilers.
Figure 1 - Boiler Ratings and Capacities
Number of
Model
Sections
XEB-2
2
XEB-3
3
XEB-4
4
XEB-5
5
XEB-6
6
XEB-7
7
* MBH = 1,000 Btuh = British Thermal Unit Per Hour. Boilers are equipped for altitudes up to 2,000 feet only. U.S.A. Only - For altitudes above 2,000
feet, ratings should be reduced at the rate of 4% for each 1,000 feet above sea level. Canada Only - Boilers may be used at high altitude (2,000-4500
feet/640-1350m) by using a certified field conversion kit, resulting in a 10% de-rate. Contact Provincial authority having jurisdiction for installations
above 4500 ft (1350m) above sea level.
+ Heating Capacity based on D.O.E. (Department of Energy) test procedure.
New York City MEA Number 484-84-E Vol. IV.
The Ratings marked "Net I=B=R Ratings" indicate the
amount of remaining heat input that can be used to heat
the radiation or terminal units. The Net I=B=R Ratings
shown are based on an allowance of 1.15

INSTALLATION INSTruCTIONS

These instructions must be affixed on or adjacent to the boiler.

BOILEr rATINgS ANd CApACITIES

Table 1 - RATINGS NATURAL AND PROPANE GASES
Heating
Input *MBH
Capacity *MBH
42.5
36
75.0
63
112.5
94
150.0
125
187.5
155
225.0
186
Improper installation, adjustment, alteration,
service or maintenance can cause injury or
!
property damage. Refer to this manual. For
assistance or information consult a qualified
installer, service agency or the gas supplier.
Net I=B=R
Width
Rating *MBH
A
31
11
55
14-1/4
82
17-1/2
109
20-3/4
135
24
162
27-1/4
Selection of boiler size should be based upon "Net I=B=R
Rating" being equal to or greater than the calculated heat
loss of the building.
The manufacturer should be consulted before selecting a
boiler for installations having unusual piping and pickup
requirements.
3
WARNING
Vent Diameter (Inches)
To Chimney
Horizontal Vent
(Category I)
(Category III)
4
3
4
3
4
3
4
3
4
4
4
4