Cable mm2 Dimensions Torque value Model D (mm) L (mm) Growatt 10000HYP 54.2 7~12 Nm WARNING: Be sure the length of all battery cables is the same. Otherwise, there will 1.Parallel communication port be voltage difference between inverter and battery to cause parallel inverters not 2.Current sharing port...
Torque Model AWG no. Load (W) -section 800Ah (min) 1200Ah (min) Growatt 10000HYP 5,000 10~8 AWG 5.5~10 mm2 1.4~1.6Nm 10,000 You need to connect the cables of each inverter together. Take the battery cables for example. You need to use a connector or bus-bar as a joint to connect the battery 15,000 cables together, and then connect to the battery terminal.
Communication Connection Use SNMP card to synchronize the parameters: Each inverter should be installed one SNMP card. Make sure all of the SNMP cards are connected to the router as a LAN. Three inverters in parallel: Power Connection Use Modbus card to synchronize the parameters: Each inverter should be installed one Modbus card.
Page 5
Launch SolarPowerPro in computer and select Device Control >> Parameter Setting >> Parallel output. Two options: Enable or Disable. Parallel for output: Disable If you want to use parallel function, please choose “Enable” and press “ ” button. Then, “ ”...
Fault code display: LCD display in Master unit LCD display in Slave unit Icon on Fault Code Fault Event Over current on Neutral wire Power feedback protection Relay board driver loss NOTE: Master and slave units are randomly defined. Warning 02 is AC GRID voltage low.
9 Trouble shooting Situation Solution Fault Code Fault Event Description 1.Remove excessive loads. Over current on Neutral 2.Restart the inverter. wire 3.If the problem remains, please contact your installer. 1.Restart the inverter. 2.Check if L1/L2/L3/N cables are not connected with wrong sequence in all Current feedback into inverters.