Braeburn 5020 Detailed Installer Manual page 11

Single stage heat / cool conventional or heat pump
Hide thumbs Also See for 5020:
Table of Contents

Advertisement

No. Installer Setting
(
Notes follow this table)
10 1st Stage Fan Control
[note 3]
11 Emergency Heat]
Fan Control [note 4]
12 Reversing Valve
(O/B Terminal) [note 5]
13 Fossil Fuel
Backup Heat [note 4]
14 Compressor Power Outage oF CPOP
Protection
[notes 4, 6]
15 AC Power Interrupt
Warning [note 6]
16 Compressor Short
Cycle Protection [note 7]
17 Residual Cooling
Fan Delay [note 7]
18 Adaptive Recovery
[note 8]
Mode (ARM™)
19 Indoor Remote Sensor
Control* [note 9]
20 Lockout Security Level
21 Auto Changeover
Dead Band [note 10]
22 Compressor Balance
Point [notes 4,
11]
23 Auxiliary Heat Balance
Point [notes 4, 11]
24 Heat Set Point Upper Limit 90LIM
25 Cool Set Point Lower Limit 45LIM
[note 7]
*When a Braeburn
outdoor sensor is connected, the thermostat automatically recognizes it. Press PROG and HOLD at the same
®
time to display outdoor temperature.
NOTE: Additional options such as Service Monitors, setting the lock code, etc. are located in the User Settings –
See User manual for information on setting these options.
Factory
Setting
Default
Options
HG FAN 1
HG FAN 1
HE FAN 1
HE EMER
HE EMER
HG EMER
REVO
REVO
REVB
AE AUX
AE AUX
AG AUX
oF CPOP
on CPOP
AC oF MONR AC oF MONR Disables AC Power Interrupt Warning
AC on MONR Enables AC Power Interrupt Warning
5 CSCP
5, 4, 3, 2 or Select a compressor short cycle protection delay of 5,
0 CSCP
60 FAN
90, 60, 30
or 0 FAN
oF REC
oF REC
on REC
I SENS
I SENS
E SENS
A SENS
2 LOCK
2 LOCK
1 LOCK
3 BAND
2, 3, 4 or 5
BAND
NO BALC
NO BALC
15-50 BALC Select a Compressor Balance Point of 15°- 50°F
NO BALA
NO BALA
70-40 BALA Select a Auxiliary Heat Balance Point of 70°- 40° F
90-60 LIM
45-80 LIM
Comments
(More information follows this table)
Select for 1st stage Gas heating
Select for 1st stage Electric heating
Select for Electric Emergency Heat
Select for Gas Emergency Heat
Select for cool active Reversing Valve (O terminal)
Select for heat active Reversing Valve (B terminal)
Select for Electric Auxiliary heat (with compressor)
Select for Gas Auxiliary heat (without compressor)
Disables Power Outage Lockout Delay
Enables Power Outage Lockout Delay
4, 3, 2 or 0 minutes
Select a Residual Cooling Fan Delay of 90, 60,
30 or 0 seconds.
Disables Adaptive (early) Recovery mode
Enables Adaptive (early) Recovery mode
Temperature is sensed from thermostat only.
Temperature is sensed from remote sensor only.
Temperature is combined with the thermostat and
t he remote sensor.
If locked – Complete lockout is enabled
If locked – Partial lockout is enabled (SpeedBar
still functional)
Select a Dead Band of 2°, 3°, 4° or 5˚ F
(1°, 2° or 3° C) for Auto Changeover mode.
Disables Balance Points
(-9°-10° C)
Disables Balance Points
(21°- 4° C)
Select a Heat Set Point Upper Limit of 90°-60° F (32°-10° C)
Select a Cool Set Point Lower Limit of 45°-80° F (7°-27° C)
11
is
®
Installer Guide