Toshiba MMF-AP0156H-E (TR) Service Manual page 57

Hide thumbs Also See for MMF-AP0156H-E (TR):
Table of Contents

Advertisement

(Errors detected by IPDU featuring in SMMS-i standard outdoor unit - typical examples)
Check code
Outdoor 7-segment display
Sub-code
01: Compressor 1
02: Compressor 2
F13
03: Compressor 3
01: Compressor 1
H01
02: Compressor 2
03: Compressor 3
01: Compressor 1
H02
02: Compressor 2
03: Compressor 3
01: Compressor 1
H03
02: Compressor 2
03: Compressor 3
01: Compressor 1
P04
02: Compressor 2
03: Compressor 3
P07
P20
SMMS (Series 1)
04: Rotation difference error
06: Maximum rotation exceeded
08: Out of step
0A: Idc activation
0C: Fan lock
0d: Lock
0E: Sync error
0F: Control error
P22
SMMS-i (Series 4)
0..: IGBT circuit
1..: Position detection circuit error
3..: Motor lockup error
4..: Motor current detection
C..: TH sensor error
D..: TH sensor error
E..: Inverter DC voltage error
(outdoor fan)
Note: Although letters 0 to F appear
at locations indicated by "∗",
please ignore them.
01: Compressor 1
P26
02: Compressor 2
03: Compressor 3
01: Compressor 1
P29
02: Compressor 2
03: Compressor 3
Note: The above check codes are examples only, and different check codes may be displayed depending on the outdoor unit configuration
(e.g. a Super heat recovery multi system). For details, see the service manual for the outdoor unit.
Display of receiving unit
TCC-LINK
Indicator light block
central control
or main remote
OperationTimer Ready
controller
display
F13
H01
H02
H03
P04
P07
P20
P22
P26
P29
– 57 –
Typical fault site
Flash
Error in temperature
sensor built into indoor
ALT
IGBT (TH)
Compressor breakdown
Compressor error (lockup)
Current detection circuit
error
Activation of high-pressure
ALT
SW
Heat sink overheating
ALT
error
ALT High-pressure protection
activation
ALT
Outdoor fan IPDU error
Activation of G-Tr (IGBT)
ALT
short-circuit protection
Compressor position
ALT
detection circuit error
Description of error
Temperature sensor built into indoor IGBT (TH)
has been open / short-circuited.
Inverter current (Idc) detection circuit detects
overcurrent.
Compressor lockup is detected
Abnormal current is detected while inverter
compressor is turned off.
High-pressure SW is activated.
Temperature sensor built into IGBT (TH) detects
overheating.
High-pressure (Pd) sensor detected a value over
the criteria.
Outdoor fan IPDU detects error.
Short-circuit protection for compressor motor
driver circuit components is activated (momentary
overcurrent).
Compressor motor position detection error is
detected.