Toshiba MMF-AP0156H-E (TR) Service Manual page 71

Hide thumbs Also See for MMF-AP0156H-E (TR):
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
controller
Sub-code
code
L18
L18
L20
L28
L28
SMMS (Series 1)
01: A3-IPDU1
error
02: A3-IPDU2
error
03: A3-IPDU1/
A3-IPDU2 error
04: Fan IPDU
error
05: A3-IPDU1 +
Fan IPDU error
06: A3-IPDU2 +
Fan IPDU error
07: All IPDU
error or
Communication
error between
IPDU and I/F
circuit board or
Outdoor I/F
circuit board error
L29
L29
SMM-i (Series 4)
A3-IPDUFan
IPDU
1
2
3
01
O
02
O
03
O
O
04
O
05
O
O
06
O
O
07
O
O
O
08
O
09
O
O
0A
O
O
0B
O
O
O
0C
O
O
0D
O
O
O
0E
O
O
O
0F
O
O
O
O
80
Symbol O
signifies site of
IPDU error.
Detected indoor
address
L30
L30
L31
P01
Location
of
Description
detection
I/F
Cool / heat switch
Only the target
unit error
unit stopped
AI-NET
Duplicated central
All stop
Indoor unit
control address
I/F
Too many outdoor
All stop
units connected
I/F
Error in No. of
All stop
IPDUs
Indoor unit External interlock
Stop of
of indoor unit
corresponding unit
I/F
Extended IC error Continued
operation
Indoor unit Indoor fan motor
Stop of
error
corresponding unit
Error detection
System status
condition(s)
The heating operation was
performed without the coolonly
setting configured in a cool-
only room where a cool / heat
switch unit is not connected.
There is duplication in central
control address setting.
There are more than four
outdoor units.
Insufficient number of IPDUs
are detected when power is
turned on.
• Signal is present at external
error input terminal (CN80)
for 1 minute.
There is part failure in P.C.
board (I/F).
– 71 –
Check items (locations)
• Check the remote controller setting.
(DN="0F")
• Check the cool / heat switching unit.
• Check the piping connection of the
switching unit.
(Miswiring of discharge gas /
suction gas)
• Check the SVS / SVD valve
miswiring / misinstallation.
• Check central control addresses.
• Check network adaptor P.C. board
(applicable to AI-NET).
• Check No. of outdoor units
connected (Only up to 4 units per
system allowed).
• Check communication lines
between outdoor units.
• Check for defect in outdoor P.C.
board (I/F).
• Check model setting of P.C. board
for servicing outdoor I/F P.C. board.
• Check connection of UART
communication connector.
• Check A3-IPDU, fan IPDU, and I/F
P.C. board for defect.
When external device is connected
to CN80 connector:
1) Check for defect in external device.
2) Check for defect in indoor P.C.
board.
When external device is not
connected to CN80 connector:
1) Check for defect in indoor P.C.
board.
Check outdoor P.C. board (I/F).
• Check the lock of fan motor
(AC fan).
• Check wiring.