20 Troubleshooting
▪ Operation of the unit is assumed to be 10  hours/day and
2,500 hours/year.
NOTICE
▪ The table indicates main components. Refer to your
maintenance and inspection contract for more details.
▪ The
table
indicates
maintenance cycles. However, in order to keep the unit
operational as long as possible, maintenance work may
be required sooner. Recommended intervals can be
used for appropriate maintenance design in terms of
budgeting
maintenance
Depending on the content of the maintenance and
inspection contract, inspection and maintenance cycles
may in reality be shorter than listed.
19.4.4
Shortened maintenance and replacement
cycles
Shortening of "maintenance cycle" and "replacement cycle" needs to
be considered in following situations:
The unit is used in locations where:
▪ Heat and humidity fluctuate out of the ordinary.
▪ Power fluctuation is high (voltage, frequency, wave distortion, etc.)
(the unit cannot be used if power fluctuation is outside the
allowable range).
▪ Bumps and vibrations are frequent.
▪ Dust, salt, harmful gas or oil mist such as sulphurous acid and
hydrogen sulfide may be present in the air.
▪ The machine is started and stopped frequently or operation time is
long (sites with 24 hour air-conditioning).
Recommended replacement cycle of wear parts
Component
Inspection
Air filter
High efficiency filter
Fuse
Crankcase heater
Pressure containing parts
NOTICE
▪ The table indicates main components. Refer to your
maintenance and inspection contract for more details.
▪ The
table
indicates
replacement cycles. However, in order to keep the unit
operational as long as possible, maintenance work may
be required sooner. Recommended intervals can be
used for appropriate maintenance design in terms of
budgeting maintenance and inspection fees. Contact
your dealer for details.
INFORMATION
Damage due to taking apart or cleaning interiors of units by
anyone other than our authorised dealers may not be
included in the warranty.
20
Troubleshooting
If one of the following malfunctions occur, take the measures shown
below and contact your dealer.
Installer and user reference guide
66
recommended
intervals
and
inspection
fees.
Maintenance cycle
cycle
(replacements and/or
repairs)
1 year
5 years
1 year
10 years
8 years
In case of corrosion,
contact your local dealer.
recommended
intervals
WARNING
Stop operation and shut off the power if anything
unusual occurs (burning smells etc.).
Leaving the unit running under such circumstances may
cause breakage, electric shock or fire. Contact your dealer.
of
The system must be repaired by a qualified service person:
Malfunction
If a safety device such as a fuse, a
breaker or an earth leakage breaker
frequently actuates or the ON/OFF
switch does not properly work.
If water leaks from the unit.
The operation switch does not work
well.
If the user interface display indicates the
unit number, the operation lamp flashes
and the malfunction code appears.
If the system does not properly operate except for the above
mentioned cases and none of the above mentioned malfunctions is
evident, investigate the system according to the following
procedures.
Malfunction
If the system does not
operate at all.
If the system goes into
fan only operation, but
as soon as it goes into
heating or cooling
operation, the system
stops.
The system operates
but cooling or heating
is insufficient.
of
Measure
Turn off the main power
switch.
Stop the operation.
Turn off the power.
Notify your installer and
report the malfunction
code.
Measure
▪ Check if there is no power failure. Wait
until power is restored. If power failure
occurs during operation, the system
automatically restarts immediately after
the power supply is recovered.
▪ Check if no fuse has blown or breaker
has worked. Change the fuse or reset the
breaker if necessary.
▪ Check if air inlet or outlet of outdoor or
indoor unit is not blocked by obstacles.
Remove any obstacle and make it well-
ventilated.
▪ Check if the user interface display shows
(time to clean the air filter). (Refer to
"19  Maintenance
and
service"  on
page 64
and "Maintenance" in the indoor
unit manual.)
▪ Check if air inlet or outlet of outdoor or
indoor unit is not blocked by obstacles.
Remove any obstacle and make it well-
ventilated.
▪ Check if the air filter is not clogged (refer
to "Maintenance" in the indoor unit
manual).
▪ Check the temperature setting.
▪ Check the fan speed setting on your user
interface.
▪ Check for open doors or windows. Shut
doors and windows to prevent wind from
coming in.
▪ Check if there are too many occupants in
the room during cooling operation. Check
if the heat source of the room is
excessive.
▪ Check if direct sunlight enters the room.
Use curtains or blinds.
▪ Check if the air flow angle is proper.
RXYSQ8~12TMY1B
VRV IV-S system air conditioner
4P404225-1B – 2016.03