5.3.3

To select the piping size

Determine the proper size referring to following tables and reference
figure (only for indication).
INFORMATION
▪ Combination of VRV DX and RA DX indoor units is not
allowed.
▪ Combination of RA  DX and AHU indoor units is not
allowed.
▪ Combination of RA DX and aircurtain indoor units is not
allowed.
INFORMATION
In case of RXYSQ8: If you install RA DX indoor units, you
have to configure field setting [2‑41] (=  type of installed
indoor units). See
"7.2.8  Mode 2: Field settings"  on
page 33.
In case of RXYSQ10+12: The type of indoor units is
detected automatically.
VRV DX
1
A
2
B-1
B-2
2
2
C-1
C-2
C-3
C-4
3-1
3-2
3-3
3-4
1
Outdoor unit
2
Refrigerant branch kits
3-1~3-4
VRV DX indoor units
4
BP units
5
RA DX indoor units
A
Piping between outdoor unit and (first) refrigerant branch
kit
B-1 B-2
Piping between refrigerant branch kits
C-1~C-4
Piping between refrigerant branch kit and indoor unit
D
Piping between refrigerant branch kit and BP unit
E
Piping between BP unit and RA DX indoor unit
In case the required pipe sizes (inch sizes) are not available, it is
also allowed to use other diameters (mm sizes), taken the following
into account:
▪ Select the pipe size nearest to the required size.
▪ Use the suitable adapters for the change-over from inch to  mm
pipes (field supply).
▪ The additional refrigerant calculation has to be adjusted as
mentioned in
"6.7.3  To determine the additional refrigerant
amount" on
page 24.
A: Piping between outdoor unit and (first)
refrigerant branch kit
When the equivalent pipe length between outdoor and indoor units is
90  m or more, the size of the main pipes (both gas side and liquid
side) must be increased. Depending on the length of the piping, the
capacity may drop, but even in such a case the size of the main
pipes has to be increased. More specifications can be found in the
technical engineering data book.
RXYSQ8~12TMY1B
VRV IV-S system air conditioner
4P404225-1B – 2016.03
RA DX
1
A
2
D
D
4
4
E
E
E
E
5
5
5
5
a
b
c
d
a
Outdoor unit
b
Main pipes
c
Increase
d
First refrigerant branch kit
e
Indoor unit
Outdoor unit
Piping outer diameter size (mm)
capacity type (HP)
Gas pipe
Standard
8
19.1
10
22.2
(b)
12
25.4
(a)
If size is NOT available, increase is NOT allowed.
(b)
If size is NOT available, increase to 28.6 mm is allowed.
B: Piping between refrigerant branch kits
Choose from the following table in accordance with the indoor unit
total capacity type, connected downstream. Do not let the
connection piping exceed the refrigerant piping size chosen by the
general system model name.
Indoor unit capacity
Piping outer diameter size (mm)
index
Gas pipe
<150
150≤x<200
200≤x<290
290≤x<390
Example: Downstream capacity for B-1 = capacity index of unit 3-1
+ capacity index of unit 3-2
C: Piping between refrigerant branch kit and
indoor unit
Use the same diameters as the connections (liquid, gas) on the
indoor units. The diameters of the indoor units are as follows:
Indoor unit capacity
Piping outer diameter size (mm)
index
Gas pipe
15~50
63~140
200
250
D: Piping between refrigerant branch kit and BP
unit
Total capacity index
Piping outer diameter size (mm)
of connected indoor
Gas pipe
units
15~62
63~149
150~208
5 Preparation
e
Liquid pipe
Size-up
Standard
Size-up
22.2
9.5
12.7
(a)
25.4
28.6
12.7
15.9
Liquid pipe
15.9
9.5
19.1
22.2
28.6
12.7
Liquid pipe
12.7
6.4
15.9
9.5
19.1
22.2
Liquid pipe
12.7
6.4
15.9
9.5
19.1