Parameter Function
P944
Reset to factory default settings
P971 ·
EEPROM storage control
G85139-H1751-U529-D1
4/8/99
Range
Description / Notes
[Default]
0 - 1
Set to '1' and then press P to reset all parameters except P101 to the factory
[0]
default settings. Previously set parameters will be overwritten including the
motor parameters P080 - P085 (See section 4.2)
0 - 1
0 = Changes to parameter settings (including P971)
[1]
are lost when power is removed.
1 = Changes to parameter settings are retained during periods
when power is removed.
IMPORTANT:
held in EEPROM, care must be taken not to exceed the maximum number
of write cycles to this EEPROM - this is approximately 50,000 write
cycles. Exceeding this number of write cycles would result in corruption
of the stored data and subsequent data loss. The number of read cycles
are unlimited.
62
6. SYSTEM PARAMETERS
When using the serial link to update the parameter set