Parameter Function
P040 ·
Positioning function
P041 ·
Fixed frequency 1 (Hz)
P042 ·
Fixed frequency 2 (Hz)
P043 ·
Fixed frequency 3 (Hz)
P044 ·
Fixed frequency 4 (Hz)
G85139-H1751-U529-D1
4/8/99
Range
Description / Notes
[Default]
0 - 1
0 - Disabled
[0]
1 - Under normal operation the ramp-down time is defined as the time taken
to ramp-down from the value set in P013 to 0. Setting P040 to 1 will
automatically re-scale the ramp down time so that the motor will always stop
in the same position regardless of operating frequency.
f
P013
0
e.g. P003 = 1s, P013 = 50Hz, P012 = 0Hz.
If the motor is running at 50Hz and a stop command applied, the motor will
stop in 1second. If the motor is running at 25Hz, the motor will stop in 2
seconds and if the motor is running at 5Hz, the motor will stop in 10 seconds.
In each case, the motor will stop at the same position.
0 - 650.00
Valid if P006 = 2 and P055 = 6 or 18, or P053-55=17
[5.00]
0 - 650.00
Valid if P006 = 2 and P054 = 6 or 18, or P053-55=17
[10.00]
0 - 650.00
Valid if P006 = 2 and P053 = 6 or 18, or P053-55=17
[15.00]
0 - 650.00
Valid if P006 = 2 and P052 = 6 or 18 , or P053-55=17
[20.00]
48
6. SYSTEM PARAMETERS
Stop Command
0
t
Stop position
© Siemens plc 1999