Chapter 4 Parameters|
Settings
Function
6
Accel/Decel Inhibit
Accel/Decel Time
7
Selection
Command
Jog Operation
8
Control
4-90
Description
When the command is active, acceleration and deceleration is
stopped and the AC motor drive maintains a constant speed.
Frequency
setting
frequency
accel. inhibit
accel . i nhibi t
actual operation frequency
ON
M Ix-GND
operation
command
Used to select the one of 2 Accel/Decel Times (Pr.01.09 to
Pr.01.12).
Frequency
setting
01.09
frequency
MI -GND
x
operation
ON
command
Parameter value 08 programs one of the Multi-function Input
Terminals MI3 ∼ MI6 (Pr.04.05~Pr.04.08) for Jog control.
NOTE: Programming for Jog operation by 08 can only be
done while the motor is stopped. (Refer to parameter
Pr.01.13~Pr.01.15)
01.15
Jog frequency
01.05
Min. output
frequency
Jog accel. time
01.13
MIx -GND
decel. inhibit
ON
ON
ON
01.11
01.09
00.10
01.12
ON
ON
ON
Revision Jan. 2009, 06EE, SW--PW V1.12/CTL V2.12
actual operation
frequency
decel. inhibit
Time
ON
OFF
01.12
Time
ON
ON
OFF
Jog decel. time
01.14
OF F