1.1.1 Sensor calibration: DIP switch 1

Set the DIP switch to ON and press the DIP switch reset button:
The display shows CAL. The room temperature currently acquired
blinks.
Press
or
to make a recalibration of max. ± 5 °C. To save
the entry, set the DIP switch to OFF and press the DIP switch reset
button (also refer to Fig.
).

1.1.2 Setpoint limitation: DIP switch 2

DIP switch ON:
Setpoint limitation 16...35 °C
DIP switch OFF:
Setpoint limitation 3...35 °C
(factory setting)
Save the entry by pressing the DIP switch reset button.
1.1.3 Temperature display in °C or °F:
DIP switch 3
DIP switch ON:
Temperature display in °F
DIP switch OFF:
Temperature display in °C
(factory setting)
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
).
1.1.4 Control action: DIP switches 4 and 5
DIP switch 4 ON and 5 ON:
Adaptive control for all types of application.
DIP switch 4 ON and 5 OFF:
2

Accessing the expert level

Move the selector slider to the RUN position and press simultaneously
seconds, press simultaneously
access the expert level for making the settings on that level.
Starting with code 00, the display shows the choice of languages. Navigation on the expert level is made possible with
the settings by pressing
.
The expert level is quit by pressing the operating mode selection button
Code list
Function block
Code
00
Basic settings
01
02
10
LCD settings
11
12
30
Clock settings
31
32
Note 1:
If the radio clock is not active or not present, this setting has no impact.
With the radio clock active, the time signal received from Frankfurt is shifted by the value set under code 30 (time zone).
Note 2:
If the radio clock is not active or not present, the time change always takes place at 02:00 on the Sunday before the set date.
With the radio clock active, the time change is shifted by the value set under code 30 (time zone).
Note 3:
If the radio clock is not active or not present, the time change always takes place at 03:00 on the Sunday before the set date.
With the radio clock active, the time change is shifted by the value set under code 30 (time zone).
CE1G2201xx
PID self-learning
PID 6
and
for 3 seconds, release
Name
Language
Sensor calibration
Switching differential 2-point
Illumination time
Background brightness
Contrast
Time zone
Deviation from time signal received from
Frankfurt (Central European Time CET)
(refer to Note 1)
Start of summer time (refer to Note 2)
End of summer time (refer to Note 3)
2015-02-27
For fast controlled systems, applications at locations with
great temperature variations.
DIP switch 4 OFF and 5 ON:
For normal controlled systems, applications at locations
with normal temperature variations.
DIP switch 4 OFF and 5 OFF:
For difficult controlled systems, 2-position controller with a
switching differential of 0.5 °C (factory setting).
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
).
1.1.5 Radio clock: DIP switch 6
Can only be used with REV..DC (with integrated DCF77 receiver
for time signal from Frankfurt)!
DIP switch ON:
Clock runs on built-in
DIP switch OFF:
Frankfurt
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
).
1.1.6 DIP switch reset
When changing one or several DIP switch positions, press the DIP
switch reset button to make a DIP switch reset.
Otherwise, the previous settings will be maintained!
(Also refer to Fig.
).
and
for 3 seconds, then release the buttons and, within 3
and keep
depressed for another 3 seconds. This enables you to
on display (also refer to Fig. G).
.
Factory setting
English
off
0.5 °C
10 seconds
0
0
0 hours
March 31 (31-03)
October 31 (31-10)
PID 12
2-Point
quartz
Time signal DCF77 from
and
. Confirm
Your setting
DE
EN
FR
IT
NL
ES
PT
CS
HU
PL
SV
FI
DA
TR
EL
7/49

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents