Flow Chart Of Troubleshooting; High-Pressure Protection - Gree GMV-PD100W/NAB-K Service Manual

Dc inverter multi vrf
Table of Contents

Advertisement

DC Inverter Multi
VRF Service Manual

2 FLOW CHART OF TROUBLESHOOTING

2.1 High-pressure Protection

High-pressure protection
Use pressure gauge to
measure if the pressure is
really high?
Check if the operation mode of
indoor unit is set properly?
Check if the gas valve and
liquid valve are fully open?
Check if the front panel of
outdoor unit is covered tightly?
Check if the air inlet and
outlet of the indoor and
outdoor exchanger is
smooth?
Check if the indoor and
outdoor fans run normally?
Check if the indoor swing
louver is fully open?
Check if the capacity output of
outdoor unit is equal to the
capacity demand of indoor
units?
Check if the indoor electronic
expansion valve can work
normally
Check if the indoor / outdoor
filters or radiating fins are dirty
or blocked?
The system pipe is blocked
98
No
Measure if the pressure switch
Yes
No
Refer to the Instruction
Manual for Indoor Unit
Yes
No
Fully open the valve
Yes
No
Cover up the front panel properly
Yes
No
Remove the obstructions
Yes
No
Measure the fan motor
and signal input
Yes
No
Measure the swing motor and signal
Yes
No
Refer to the dial-up of indoor and outdoor unit
Yes
No
Engage the valve body with the coil
Yes
Yes
Refer to the Repair and Maintenance
No
Focus on checking the inlet and outlet of the connection between indoor units
and main pipe. Also focus on checking the electronic expansion valve of indoor
unit and outdoor unit. Replace the electronic expansion valve, drying filter and
other parts
Yes
Replace the mainboard
is normal
of outdoor unit
No
Replace the pressure switch
input