Gree GMV-PD100W/NAB-K Service Manual page 58

Dc inverter multi vrf
Table of Contents

Advertisement

DC Inverter Multi
VRF Service Manual
2) Dimension:
The following dimension is for reference. The cabinet is designed according to 10 communication modules
into. If more modules are needed, the cabinet should be designed once again. The internal structure should
accord to actual state.
The external dimension of the cabinet (Unit: mm)
3) Installation Criteria:
The dimension of the cabinet should be designed according to quantity , arrangement and put position
of the communication modules before make of it.
Independent power supply for each communication module is needed, so enough 220v AC sockets
should be installed in the cabinet.
The communication cable and heavy-current wire should be separated for the distance above 15cm.
The cabinet should be put indoors and locked to avoid insolation and rainwater or contact of non-
manager.
8.3.5 3-way Phone Connector (user provided parts)
Note: Lines without 3-way telephone connector can be connected by welding and protected with
insulating tape to avoid oxidization and short circuit.
54
800
730