Display Code On Digital Tube Of Outdoor Mainboard - Gree GMV-PD100W/NAB-K Service Manual

Dc inverter multi vrf
Table of Contents

Advertisement

Outdoor ambient
F4
temperature
sensor error
Outdoor defrost
F7
temperature
sensor error
Exhaust
F9
temperature
sensor error

1.2 Display Code on Digital Tube of Outdoor Mainboard

Error
DC overvoltage protection
Module overheat protection
Current test circuit fault
Module temperature sensor fault
Compressor overcurrent protection
DC undervoltage protection
Compressor startup failure
PFC module protection
Drive resetting and stop
Protection of compressor against
loss of synchronization
Compressor protection
against loss of phase
Inverter drive communication fault
IPM module protection
Test for 30 seconds successively to check if the temperature sensor is disconnected.
If yes, alarm will be sent; otherwise no processing will be made. If the controller
of outdoor unit detects failure of outdoor sensor under open circuit, short circuit
Outdoor
and excess of test value, the outdoor unit will execute the following default
environment
actions, that is, the error message will be sent to each indoor unit and the error
sensor
code will be displayed via error indicator or wired controller. When the outdoor
ambient temperature is lower than -5 , the disconnection failure of outdoor
inlet, middle and exit sensors in shield room will be processed as under -30 .
Test for 30 seconds successively to check if the temperature sensor is disconnected.
If yes, alarm will be sent; otherwise no processing will be made. If the controller
of outdoor unit detects failure of outdoor sensor under open circuit, short circuit
Outdoor Defrost
and excess of test value, the outdoor unit will execute the following default
Sensor
actions, that is, the error message will be sent to each indoor unit and the error
code will be displayed via error indicator or wired controller. When the outdoor
ambient temperature is lower than -5 , the disconnection failure of outdoor
inlet, middle and exit sensors in shield room will be processed as under -30 .
Test for 30 seconds successively to check if the temperature sensor is disconnected.
If yes, alarm will be sent; otherwise no processing will be made. If the controller
of outdoor unit detects failure of outdoor sensor under open circuit, short circuit
Exhaust
and excess of test value, the outdoor unit will execute the following default
temperature
actions, that is, the error message will be sent to each indoor unit and the error
sensor
code will be displayed via error indicator or wired controller. When the outdoor
ambient temperature is lower than -5 , the disconnection failure of outdoor
inlet, middle and exit sensors in shield room will be processed as under -30 .
Display
Display on
on Digital
Indoor Unit
Tube
PH
E5
P8
E5
Pc
E5
P7
E5
P5
E5
PL
E5
Lc
E5
Hc
E5
P0
E5
H7
E5
Ld
E5
P6
E5
H5
E5
Error
Input overcurrent protection
Jumper fault
Recharging circuit fault
High-pressure protection
Low-pressure protection
Exhaust protection
Compressor overload protection
Communication fault (between indoor
/ outdoor unit and wired controller)
Outdoor ambient temperature
sensor error
Indoor coil inlet temperature
sensor error
Indoor coil middle temperature
sensor error
Outdoor coil outlet
temperature sensor error
Exhaust temperature sensor error
DC Inverter Multi
VRF Service Manual
Display
on
Display on
Digital
Indoor Unit
Tube
PA
E5
C5
No display
PU
E5
E1
E1
E3
E3
E4
E4
H3
E5
E6
E6
F4
F4
F5
F5
F6
F6
F7
F7
F9
F9