BATTERY Indicator Lights: These three lights will illuminate in several sequences to show the approximate charge level of your connected
battery bank and alert you to two fault conditions:
Approximate Battery Charge Level*
Indicator Illuminated
Green
1
Green & Yellow
2
3
Yellow
4
Yellow & Red
Red
5
All three lights off
6
Flashing red
7
* Charge levels listed are approximate. Actual conditions vary depending on battery condition and load.
Fault Condition
Indicator Illuminated
1
All three lights flash slowly*
All three lights flash quickly**
2
*Approximately ½ second on, ½ second off. See Troubleshooting section.
** Approximately ¼ second on, ¼ second off. May also indicate a battery charger fault exists. See Troubleshooting section.
Resetting Your Inverter/Charger to Restore AC Power
Your Inverter/Charger may cease supplying AC power or DC charging power in order to protect itself from overload or to protect your
electrical system. To restore normal functioning:
Overload Reset: Switch operating mode switch to "OFF" and remove some of the connected electrical load (i.e., turn off some of the AC
devices drawing power which may have caused the overload of the unit). Wait one minute, then switch operating mode switch back to
either "AUTO/REMOTE" or "CHARGE ONLY".
Battery Capacity
(Charging/Discharging)
91%–Full
81%–90%
61%–80%
41%–60%
21%–40%
1%–20%
0% (Inverter shutdown)
Fault Condition
Excessive discharge (Inverter shutdown)
Overcharge (Charger shutdown)
6
1
2
3
4
5
6
7
1