Combustible Mantel; Clearances; Gas Connection; Venting - Regency Sunrise U32S-NG5 Owners & Installation Manual

Gas insert
Hide thumbs Also See for Sunrise U32S-NG5:
Table of Contents

Advertisement

coMBustiBle Mantel

clearances

12
10
8
18
16
47"
(1194mm)
14
to ceiling
12
10
17"
8
6
4
2
0
20"
to floor
Due to the extreme heat this fireplace emits,
the mantel clearances are critical.
Note: A non-combustible mantel may be
installed at a lower height if the
framing is made of metal studs
covered with a non-combustible
board.
Mantel can be installed anywhere in shaded area
or higher using the above scale.
note: ensure the paint that is used
on the mantel and the facing is
"heat resistant" or the paint may
discolour.
U32S-5 FPI Direct Vent Gas Insert

Gas connection

Gas connection WarninG:
Only persons licensed to work
G
with gas piping may make the
6
4
2
necessary gas connections
12" Mantel
1) If the appliance is to be installed into an
3-1/2"
existing chimney system, thoroughly clean
Mantel
the masonry or factory built fireplace.
2) The appliance is provided with an opening on
the left hand side of the control compartment.
A 3/8" NPT gas supply pipe must be brought
near this inlet hole.
3) Locate the center point where the vent
13"
will pass through the chimney above the
appliance. Move the appliance into the
exact location where it is to be installed.
Ensure that the Insert is level.
Top of
Unit
Side View
Gas
Inlet
tHe appliance Must not Be
cHiMneY flue serVinG a
This appliance is designed to be attached to
two 3" (76mm) co-linear aluminium flex running
the full length of the chimney. The flue length
must be a minimum length of 8 ' (2.44m) and
a maximum of 35' (10.7m). See chart below for
minimum distances from roof. Periodically check
that the vent is unrestricted.
Masonry chimneys may take various contours
which the flexible liner will accommodate.
However, keep the flexible liner as straight as
possible, avoid unnecessary bending.
The Air Intake pipe must be attached to the inlet
air collar of the termination cap.
part #
948-305
946-529
to this appliance.
C L

VentinG

connected to a
separate solid fuel
BurninG appliance.
description
3" Flex - 35 ft.
Co-linear DV Vertical
Termination Cap
installation
alternate approved caps
46dva-VC
Vertical Termination Cap
46dva-VCH High Wind Cap
46dva-GK
3" Co-linear Adaptor with flashing
In areas of consistently high winds, we
recommend using the Simpson Dura-Vent
System (46dva-GK adapter and 46dva-VCH
high-wind cap).
The Air Intake pipe must be attached to the
inlet air collar of the termination cap.
11