Mitsubishi Electric PCFY-P40VGM-E Technical & Service Manual page 18

Split-type, heat pump air conditioners
Hide thumbs Also See for PCFY-P40VGM-E:
Table of Contents

Advertisement

<Thermistor Characteristic graph>
Thermistor at
lower temperature
Thermistor R
=15k' ± 3%
0
Fixed number of B=3480K ± 2%
1
Rt=15exp { 3480(
273+t
0:
15k'
10:
9.6k'
20:
6.3k'
25:
5.4k'
30:
4.3k'
40:
3.0k'
Linear expansion valve
1 1 Operation summary of the linear expansion valve.
• Linear expansion valve open/close through stepping motor after receiving the pulse signal from the indoor controller board.
• Valve opening can be changed in proportion to the number of pulse signal.
<Connection between the indoor controller board and the linear expansion valve>
Linear expansion valve
4
Blue
Brown
M
6
Yellow
2
5
1
3
Red
White
Orange
Note : Since the number of the connector at the controller board side and the relay connector are different, follow the color of
the lead wire.
Room temperature thermistor(TH21)
Liquid pipe temperature thermistor(TH22)
Gas pipe temperature thermistor(TH23)
1
) }
273
[4
[3
[2
[1
50
40
30
20
10
0
Relay connector
2
Brown
5
Red
1
Blue
3
Orange
4
Yellow
6
White
Connector(CN60)
18
< Thermistor at lower temperature >
-20
-10
0
10
20
30
Temperature (:)
Controller board
DC12V
6
5
Drive circuit
[4
4
[3
3
[2
2
[1
1
40
50

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pcfy-p100vgm-ePcfy-p63vgm-ePcfy-p125vgm-e

Table of Contents