Page 4
Meaning of model name E F Y - VML E Packaged Sub name Air conditioner Model size ·20 : 0.8HP ·100 : 4.0HP Series ·25 : 1.0HP ·125 : 5.0HP ·L : Ceiling cassette ·32 : 1.25HP ·140 : 6.0HP ·E : Ceiling concealed ·40 : 1.6HP ·200 : 8.0HP...
4. Electrical Wiring Diagram FUSE BREAKER PULL BOX (15A) (15A) POWER SUPPLY TO OUTDOOR UNIT TO NEXT ~/N 220-230-240V 50Hz BC CONTROLLER INDOOR UNIT 220V 60Hz REMOTE CONTROLLER DC24-30V TB2 L M1 M2 (SHIELD) TO MA-REMOTE CONTROLLER DC8.7-13V TB15 CN3A CN2M (BLU) (BLU)
4. Electrical Wiring Diagrams G PLFY-P32~125VAM-E <SYMBOL EXPLANATION> SYMBOL NAME SYMBOL NAME SYMBOL NAME INDOOR POWER BOARD CAPACITOR(FAN MOTOR) PIPE TEMPERA TURE DETECTION / GAS INDOOR CONTROLLER BOARD FAN MOTOR(WITH INNER THERMO) TH23 THERMISTOR (0˚C/15kΩ, 25˚C/5.4kΩ) CN25 HUMIDIFIER VANE MOTOR CN32 REMOTE SWITCH DRAIN WATER LIFTING-UP MACH...
6. Options Description Model Applicable capacity P32~P125 Decoration panel PLP-6AA Air outlet shutter plate P32~P125 PAC-SG06SP-E PAC-SE13KF-E P32~P125 (PAC-SE21TM-E is High efficiency filter element necessary to use this filter) PAC-SG01KF P32~P125 Multi-function casement PAC-SG03TM-E P32~P125 1- 103...
4. Electrical Wiring Diagrams 4-1 PKFY-P-VAM-E <SYMBOL EXPLANATION> Symbol Name Symbol Name Symbol Name Indoor controller board Power supply Pipe temp. detection/Gas Thermistor Terminal block TH23 (0˚C / 15kΩ, 25˚C / 5.4kΩ) CN32 Remote switch MA-Remote controller CN41 HA terminal - A Indoor power board Circuit board Address...
5. Temperature/Airflow distribution 5-1 PKFY-P-VAM-E G Temperature distribution <Cooling mode> <Heating mode> Horizontal air flow Downward air flow 27 29 Floor distance (m) Floor distance (m) G Airflow distribution <Fan mode> <Fan mode> Horizontal air flow Downward air flow Floor distance (m) Floor distance (m) 1- 112...
4. Electrical Wiring Diagram <SYMBOL EXPLANATION> Symbol Name Symbol Name Symbol Name Indoor controller board Capacitor(fan motor) Circuit board Address Remote switch Linear expansion valve Mode selection CN32 Centrally control Fan motor(with inner thermo) Voltage selection CN51 Connector Remote indication Vane motor Switch CN52...
1. Restrictions on refrigerant piping lengths 1 PUHY-P200~P650(8HP~26HP) PUY-P200~P350(8HP~14HP) Outdoor unit Branch header Indoor Indoor unit Indoor Indoor First branch unit unit unit (branch joint) Branch joint Indoor Indoor unit unit Indoor unit Notes: 1. No further branching in the pipes is possible after the header branch. 2.
Page 124
2 PUHY-P700·750·800 (28·30·32HP) Hex unit Comp unit Branch header ✕ First branch (branch joint) Indoor Indoor Indoor unit unit unit Branch joint Indoor Indoor unit unit Indoor unit Notes: 1. Mount the Hex unit on the left and Comp unit on the right. (as seen from the front of the unit) 2.
Page 125
3 PURY-P200·250·300·350 (8·10·12·14HP) Pipe Allowable Equivalent Item section length length A+B+a+b 300m max. Outdoor unit Total pipe length – ✻2 +c+d+e Farthest pipe length 150m max. 175m max. Between outdoor and 110m max. 110m max. BC controller 40m max. 40m max. Indoor - BC controllers ✻3 ✻3...
Page 126
4 PURY-P400·450·500·550·600·650 (16·18·20·22·24·26HP) Note: Connecting indoor units 141-250 capacity index. Outdoor unit Liquid pipe Gas pipe BC controller (Master) BC controller (Slave) Branch pipe CMY-Y-102S-G indoor indoor (Models 200, 250) indoor indoor (Models 141 to 250) Max.3 sets indoor units to 1 connection. Total capacity 140 and below indoor Item...
2. Refrigerant piping selection 1 PUHY, PUY Hex unit Comp unit Note : • No further branching is possible after the header branch. • Always select CMY-Y202-G for the first branch of P450~P650. • Always select CMY-Y302-G for the first branch of P700, 750, 800. Branch header ✕...
Page 128
2 PURY BC controller Outdoor unit BC controller CMY-R160-J Indoor unit BC controller Reduction (attached) Branch joint Joint pipe Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit (1) Outdoor unit - BC controller (Pipe A) • Joint pipe CMY-R160-J Outdoor unit model High press.
3. Example of refrigerant piping selection Example 1 Outdoor unit : PUHY-P200 Pipe A Select by outdoor unit capacity. (Table-1) Pipe B Liquid pipe ø 9.52 Branch header Select by total capacity of Gas pipe ø 19.05 indoor units on Select by number of downstream side.
Page 130
Example 2 Outdoor unit : PURY-P250 BC controller Joint T branch 2 T branch 3 T branch 1 Max 3 indoors for 1 connection Max 3 indoors for 1 connection Total capacity below 280 using Joint Total capacity below 140. (using 2 branches) (1) Selection of branch pipe kit (1) Selection of branch pipe kit...
4. Calculation of additional refrigerant charge 1 PUHY, PUY (1) Refrigerant charge The following amount of refrigerant is being charged into the outdoor unit at factory shipment. As the amount does not include that for extended piping, charge it additionally in the filed. •...
Page 132
2 PURY (1) Refrigerant charge The following amount of refrigerant is being charged into the outdoor unit at factory shipment. As the amount does not include that for extended piping, charge it additionally in the filed. Outdoor unit P200 P250 P300 P350 P400...