Eko Warrior ks50-dc Installation And Operating Instructions Manual page 57

Dc inverter series air to water heat pump
Table of Contents

Advertisement

STERILIZE function:
STERILIZE
DURATION
PERIOD
Water temp
level.
Duration
This allows the duration of the sterilisation process to be set to between 10 and 90 minutes. The factory
to the required level.
Period
This allows the period for the sterilisation process to be set to between 7 and 99 days. The factory default is
level. Once sterilisation has been carried out it will not be executed again until the set period has elapsed.
Time
Time: Default is 10:00 - 14:00;
NOTE:The sterilize action only will be actives during the select time period of the day.
ADD START function:
unit such as low refrigerant gas, where a maintenance engineer will need to make a temporary setting at this value.
ADD DELAY function:
This setting is for operation of the heat pump generally.
This setting fixes how long the compressor will work alone before employing the electrical heater for extra power.
The setting can be set between 2 and 90 minutes; the factory setting is 30 minutes.
TIME
10:00 - 14:00
10M
14:00 - 18:00
15D
18:00 - 22:00
22:00 - 02:00
02:00 - 06:00
06:00 - 10:00
56