WARMWATER
When this mode is ticked on the menu the hot water tank is heated. The unit stops running as soon as the
starts heating hot water again whenever the temperature drops to below the difference set by CMPDIF
ROOMHEAT
When this mode is ticked on the menu the heat pump runs according to the relationship between time and
VIA THE APPROPRIATE submenu. The setting has no effect on hot water heating.
ROOMHEAT1
ROOMHEAT2
When this mode is ticked on the menu the heat pump runs according to the room temperature. When the
the unit for this function.
NOTE: if the heating is left on during the summer the system should be set to operate in
ROOMHEAT2 mode.
WARMWATER and ROOMHEAT or
WARMWATER and ROOMHEAT1 or
WARMWATER and ROOMHEAT2
When any of these combinations are ticked on the menu, the hot water tank is heated as a priority. If no
room heating is required, the unit stops running as soon as the hot water tank's temperature reaches the
required temperature.. The unit starts heating hot water again whenever the temperature drops back.
If room heating is required, the unit switches to room heating for as long as the hot water temperature
is at the required temperature, then it automatically switches back to warm water heating to bring the
temperature back to the set limit. The amount that the temperature needs to drop back before switching
occurs is set in the TEMPERATURE submenu.
HEATPUMP
The mode is changed by pressing RIGHT when the HEATPUMP menu item is selected.
When the heat pump is OFF the indoor unit is normally still running, i.e. the water circulation pump
continues to operate, if a ROOMHEAT option is set.