move the cursor to the required value and press UP or DOWN until the required value is shown. Pressing
LEFT will confirm the change and the factory setting will be replaced by the new value.
been altered will be changed back to the factory settings.
MANUAL DEF:
start temperature of the evaporator pipe is below the set value and the set time interval has elapsed, the
compressor will go into defrost mode.
Defrost finish
is reached, the defrosting will finish.
DEF.TIME:
The duration of defrosting is adjustable between 2 to 20 minutes; the factory setting is 15 minutes.
INTERVAL:
The interval between defrosting periods is adjustable from 25 to 70 minutes; the factory setting is 40
minutes.
START TEMP:
EXIT TEMP:
SINCE TIME:
This item records the total period over which defrosting has occurred, from start time to exit time.
BETW.TIME:
This item records the interval between the ending of one defrosting period and the beginning of the next
defrosting period.
ADD DEF:
When the cursor is on this menu item, pressing RIGHT will allow the additional compressor heater to be