Fujitsu AS*G09LTCB Service Instructions Manual page 45

Split type wall mounted type inverter
Table of Contents

Advertisement

Trouble shooting 14
OUTDOOR UNIT Error Method:
Outdoor thermistor error
Detective Actuators:
Outdoor unit Main PCB
Outdoor temperature thermistor
Forecast of Cause :
1. Connector connection failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 2 :
Thermistor Characteristics (Approx. value)
Temperature
Resistance Value (k )
Temperature
Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
OK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
AO*G09/ 12LTCN
THERMISTOR
(PIPE)
BLACK
BLACK
BROWN
BROWN
THERMISTOR
(DISCHARGE)
THERMISTOR
(OUTDOOR)
BLACK
BLACK
If the voltage does not appear, replace Main PCB.
Indicate or Display:
Refer to error code table.
Detective details:
When Outdoor temperature thermistor open or short-circuit is
detected at power ON or while running the compressor.
2.Thermistor failure
-30°C
-25°C
-20°C
-15°C
224.3
159.7
115.2
84.2
15°C
20°C
25°C
30°C
16.1
12.6
10.0
8.0
AO*G14LTCN
THERMISTOR
(PIPE)
1
1
2
2
CN71
3
3
4
4
THERMISTOR
(DISCHARGE)
THERMISTOR
(OUTDOOR)
1
1
CN70
2
2
3
3
3. Main PCB failure
-10°C
-5°C
0°C
62.3
46.6
35.2
35°C
40°C
45°C
6.4
5.2
4.2
BLACK
1
1
BLACK
2
2
CN61
BLACK
3
3
BLACK
4
4
BLACK
1
1
CN62
2
2
BLACK
3
3
02-18
5°C
10°C
26.9
20.7
50°C
55°C
3.5
2.8