Fujitsu AS*G09LTCB Service Instructions Manual page 38

Split type wall mounted type inverter
Table of Contents

Advertisement

Trouble shooting 8
INDOOR UNIT Error Method:
INDOOR UNIT
Intake grille error
Detective Actuators:
Indoor unit Controller PCB
Micro switch
Forecast of Cause :
1. Micro switch failure
Check Point 1 : Check Limit switch
Check operation of Micro switch. (any blocking by dust, etc.)
Remove Micro switch and check ON/OFF switching operation by using a meter.
>>If Micro switch is detective, replace it.
OK
OK
Check Point 2 : Check Connector (CN11) / Wire
Check Point 2 :
Check loose contact of CN11 /shorted wire (pinched wire).
>>Replace Micro switch if the wire is abnormal
OK
OK
Check Point 3 : Replace Controller PCB
If Check Point 1 & 2 do not improve the symptom, change Controller PCB.
Indicate or Display:
Refer to error code table.
Detective details:
When the Micro switch is detected open while running the compressor.
2. Shorted connector/ wire
02-11
3.Controller PCB failure