AEI HA-263K Owner's Manual page 7

8-zone alarm control panel

Advertisement

!
Each code can be selected for 1 or 0
1 = Beep Enabled (Default)
0 = Beep Disabled
!
The above beep settings are for the keypad only. They have nothing concern with the beep
settings on the main circuit board. The beeps for keypad and circuit board are independent.
!
The warning beeps for Battery Low and AC Power Failure cannot be OFF and is not affected
by the above settings.
!
The confirmation beeps from the
" " & " "
SET THE RESPONSE TIME TO DETECT AN ALARM FOR EACH ZONE
RESPONSE TIME
!
The zone response time is fixed on 500mS for HA-263K, which is the value suitable for most of
the sensors' alarm output.
!
In some application environment or the nature of some sensors, shorter or longer response
time may be required for a protection zone. Please consult the sensor suppliers before setting
the time to the protection zone.
!
HA-263D allows the owner to set different response time to each protection zone
independently.
!
The 8 digit code represents the 8 protection zones. The first digit is zone 1 and the last digit is
zone 8. Owner can put the timing code into the specific digit to independently set the desired
response time for the 8 protection zones.
The Timing Codes for Response Times
1 = 25mS
2 = 250mS
3 = 500mS (Default)
4 = 750mS
22
HA-263D (START THE PROGRAMMING)
# keys are always enabled.
(Location 15)
LOCATION
RESPONES TIME
15
3 3 3 3
3 3
3 3
1 2
3 4
5
6 7
8
ZONES
7:
This terminal provides +12V output power at alarm condition with the time period
according to the setting of the alarm timer. It is suitable for energizing electronic siren or
alarm bell. The output is equipped with a 2.5A resettable fuse.
8, 9, :
This group of terminals are the connection points for the digital keypads (HA-263D). All
10,11
keypads can be connected in a parallel configuration back to these terminals and more
than one keypads can be allowed. The maximum allowed number of keypads and
keyswitches are 4.
8:
Common ground (-)
11:
+12V power common point, equipped with a 750mA resettable fuse
NOTE:
12:
This terminal is prepared for connection of keyswitches (RKS-2M) for arm-disarm control of
the Partition 1. It accepts Normally Open (N.O.) momentary type switches and is +12V
triggered. More than one switches can be connected in parallel.
13:
This terminal is prepared for connection of keyswitches (RKS-2M) for arm-disarm control of
the Partition 2. It accepts Normally Open (N.O.) momentary type switches and is +12V
VALIDATION
triggered. More than one switches can be connected in parallel.
#
NOTE:
UTILIZE THE KEY SWITCH FOR SYSTEM ARM-DISARM CONTROLS
ARM THE SYSTEM
One Touch
(>1/2 second)
DISARM THE SYSTEM
(>1/2 second)
(>1/2 second)
4
HA-263
HA-263
9:
Clock wire
No connection to these terminals are required for HA-263K
a) Terminal 12 and 13 can be connected together to one keyswitch for combined
arm-disarm control of the two partitions.
b) Hold the keyswitch in contact for more than 1/2 second to arm or disarm
Partition 1 or Partition 2. Two beeps will be generated to indicate that the
system is ready to arm.
c) If continuously hold any one of the keyswitch in contact for more than 5
seconds and ignore the 2 arming beeps will set system in Standby Mode.
KEY SWITCH
STATUS
CONTACT
!
Make arming for
partition 1 or 2
!
1st Touch
Make disarming for
partition 1 or 2
!
2nd Touch
Alarm memory is
cleared & the
system keeps in
disarmed mode
CONNECTION TERMINALS
10:
Data wire
RESULTS
!
Exit delay starts
!
Exit beep sounds if it is enabled
!
System will be armed after exit
delay expired
!
The system is disarmed and reset if
there was no alarm occurred. It is
ready for re-arming
!
The system is disarmed but with
alarm memory if there was alarm
occurred, 2nd touch is required
!
The alarm memory LEDs are off
(both the STATUS LED on keyswitch
and the zone LEDs on the keypad)
!
The system is ready for re-arming
7