GEL LEAD ACID TYPE.
DO NOT USE GATES BATTERY.
BATTERY NORMALLY NEED NOT BE
REPLACED FOR AT LEAST 3 YRS.
BATTERY CAPACITY FOR EMERGENCY
STANDBY USE AT LEAST 4 HOURS.
BLACK
BATTERY
CHARGING
12V, 4AH
+
VOLTAGE
RED
(e.g. ADEMCO
13.8VDC
No. 467)
OR 12V, 1.2AH
+
CONNECTOR TABS
USE UL LISTED LIMITED
ENERGY CABLE FOR
1
2
3
ALL CONNECTIONS
TO 110VAC
UNSWITCHED
OUTLET (24HR)
PLUG-IN
TRANSFORMER
16.5VAC, 25VA
(e.g. ADEMCO
No. 1321.
FOR COMPLETE
USE No. 1321CN
INFORMATION,
IN CANADA)
SEE INSTRUCTIONS
+
ALARM OUTPUT
10.5-13.8VDC, 2A MAX.
(600mA MAX FOR UL USAGE,
INCLUDING AUX. POWER)
STEADY FOR BURGLARY/PANIC,
PULSING FOR FIRE (e.g. USE
ADEMCO No. 740 SOUNDER,
No.702 OR 719 SIREN, OR 12V BELL)
CONNECTION OF THE FIRE ALARM SIGNAL TO A FIRE ALARM
HEADQUARTERS OR A CENTRAL STATION SHALL BE PERMITTED
ONLY WITH THE PERMISSION OF THE LOCAL AUTHORITY HAVING
JURISDICTION. THE BURGLAR ALARM SIGNAL SHALL NOT BE
CONNECTED TO A POLICE EMERGENCY NUMBER.
ALARM DEVICE MANUFACTURING CO.
A DIVISION OF PITTWAY CORPORATION
165 Eileen Way, Syosset, New York 11791
N8372V1 4/97
Copyright
1997 PITTWAY CORPORATION
©
BATTERY FUSE
(e.g. ADEMCO No. 90-12)
FOR REPLACEMENT
USE SAME VALUE
BLK
3A
RED
GRN
YEL
BLK
BLK
RED
RED
GRN
GRN
YEL
YEL
4
5
6
7
8
9
+
(ZONES 1-4 NOT PRESENT)
AUX. POWER
OUTPUT
10.5-13.8VDC
500mA MAX.
OPTIONAL:
INTERRUPTS
No. 5800TM
FOR FIRE
TRANSMITTER MODULE
(20mA)
ALARM RESET
(for No. 5827BD
NOTE:
Wireless Bidirectional Keypad)
KEYPAD
AND/OR
CURRENT
No. 4285 VOICE MODULE
(160mA)
MUST BE
AND/OR
INCLUDED
No. 7720ECP
IN AUX.
LONG RANGE RADIO
CURRENT
MAY ALSO BE CONNECTED.
DRAIN
SEE INSTRUCTIONS ACCOM-
CALCULATIONS
PANYING THOSE DEVICES.
REMOTE
KEYPAD
• MAXIMUM LOOP RESISTANCE: (EACH ZONE) 300 OHMS (PLUS EOLR)
• RESPONSE, ZONES 5, 6: 300-500MSEC
REMOTE KEYPADS
• ZONE 5 CAN BE PROGRAMMED FOR USE AS A FIRE ZONE.
SYSTEM MUST BE
SEE DIAGRAM.
PROGRAMMED WITH A
No. 5137AD OR 6139. IT NEED
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
NOT REMAIN IN SYSTEM.
OPERATION IS SUBJECT TO THE FOLLOWING TWO
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
AFTER PROGRAMMING,
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY
THE SYSTEM CAN USE:
INTERFERENCE RECEIVED, INCLUDING INTERFERENCE
No. 4127(20mA), 4137AD (60mA),
THAT MAY CAUSE UNDESIRED OPERATION.
5137AD (90mA), 6127 (20mA),
6128 (30mA), 6137 (85mA),
COMPLIES WITH FCC RULES, PART 68
6138 (100mA), OR 6139 (100mA).
FCC REGISTRATION NO. AC398U-68192-AL-E
MULTIPLE KEYPADS MAY BE
RINGER EQUIVALENCE: 0.7B.
USED, BUT USE MAX. OF 220 FT.
OF #22 WIRE OR 550 FT. OF #18.
WARNING:
WEEKLY TESTING IS REQUIRED TO
ENSURE PROPER OPERATION OF
THIS SYSTEM.
SET UNIT'S DIP SWITCH
FOR DEVICE ADDRESS
ADEMCO No. 4219
OF "1".
WIRED EXPANSION MODULE
See unit's instructions.
(8 ADD'L EOLR WIRED ZONES)
-OR-
ADEMCO No. 4229
WIRED EXPANSION/RELAY MODULE
(8 ADD'L EOLR WIRED ZONES PLUS 2
OUTPUT RELAYS)
-OR-
ADEMCO No. 4204 RELAY MODULE
(4 OUTPUT RELAYS)
AND/OR
SET RECEIVER'S
DIP SWITCH FOR
ADEMCO 4281 or 5881 Type
DEVICE ADDRESS
RF RECEIVER
OF "0".
WIRELESS ZONES
See receiver's
4281L:
UP TO 4
instructions.
4281M/5881L:
UP TO 8
5881M:
UP TO 16
4281/5881H:
UP TO 30
10
11
12
13
14
15
NOT USED
1000
1000
OHMS
OHMS
EOLR
EOLR
OWNER'S INSTRUCTION NOTICE NOT TO BE REMOVED.
AUX PWR
+
5
OUTPUT
BLK
-
TERMS
4
+
-
VIOLET
4-WIRE SMOKE
OR COMBUSTION
DETECTOR
1000
OHMS
EOLR
TO HI SIDE OF SELECTED ZONE
+
HEAT
TO ZONE 5*
ZONES 2–7
*
DETECTOR
-
TO LO SIDE OF SELECTED ZONE
*
IF PROGRAMMED FOR FIRE
16
17
18
19
20
TIP
RING
TIP
RING
(BROWN)
(GRAY)
(GREEN)
(RED)
HANDSET
INCOMING
PHONE
LINE
TELEPHONE WIRING
EARTH
(VIA RJ31X* JACK DIRECT
GROUND
CONNECT CORD)
SEE INSTRUCTIONS
*IN CANADA, CA38A JACK
FOR
DOC LOAD NO.: 3
PROPER GROUNDING
WARNING:
TO PREVENT RISK OF SHOCK,
DISCONNECT TELEPHONE LINE
AT TELCO JACK BEFORE
SERVICING THIS UNIT.
THIS EQUIPMENT SHOULD BE INSTALLED IN
ACCORDANCE WITH THE NATIONAL FIRE
PROTECTION ASSOCIATION'S STANDARD 74
(NATIONAL FIRE PROTECTION ASSOC.,
BATTERYMARCH PARK, QUINCY, MA 02269).
PRINTED INFORMATION DESCRIBING PROPER
INSTALLATION, OPERATION, TESTING,
MAINTENANCE, EVACUATION PLANNING AND
REPAIR SERVICE IS TO BE PROVIDED WITH
THIS EQUIPMENT.
VIA-30P
SE
SUMMARY OF CONNECTIONS
+
RED
EOL
POWER
SUPER-
VISION
RELAY
MODULE
A77-716B
EARTH
GROUND
TERMINAL
21
LOCATED AT
LOWER RIGHT
OF CIRCUIT
BOARD