Radiance
Direct Vent Gas Heater
®
Fig. 26 Securing Horizontal Pipe Sections
DISASSEMBLE VENT SECTIONS
To disassemble any two pieces of pipe, rotate either section
(Figure 27), so that the seams on both pipe sections are
aligned (Figure 28). They can then be carefully pulled apart.
Fig. 27 Rotate Seams for Disassembly
Fig. 28 Align and Disassemble Vent Sections
20306759
ASSEMBLY AND INSTALLATION
HORIZONTAL TERMINATION CAP
WARNING
Risk of Fire! The telescoping flue section of the termina-
tion cap MUST be used when connecting vent.
• 1
⁄
" (38 mm) minimum overlap of vent and telescop-
1
2
ing flue section is required.
Failure to maintain overlap may cause overheating and
fire.
Note: For horizontal vent runs through a combusti-
ble wall and framing dimensions, refer to appliance
installation manual.
Install the Horizontal Termination Cap
Attach slip section of cap to last vent section. Maintain 1
overlap between slip and vent sections.
Note: For installations using black pipe, slide the
decorative wall thimble over the last vent pipe
before connecting the termination to the pipe.
When this connection has been made, slide the
wall thimble up to the interior wall surface and
attach with screws provided.
Secure termination cap to exterior wall using provided
holes and fasteners.
Vent termination must not be recessed in the wall. Siding
may be brought to the edge of the cap base.
CAUTION
Risk of Burns! Local codes may require installation of a
termination guard to prevent anything or anyone from
touching the hot cap.
Flash and seal as appropriate for siding material at outside
edges of cap.
When installing a horizontal termination cap, follow the cap
location guidelines as prescribed by current ANSI Z223.1
and CAN/CGA-B149 installation codes.
⁄
"
1
2
19