Vent Termination Clearances - Vermont Castings Radiance RADVTSCCB Installation And Operating Instructions Manual

Radvt series direct vent gas heater
Hide thumbs Also See for Radiance RADVTSCCB:
Table of Contents

Advertisement

PRE-INSTALLATION

VENT TERMINATION CLEARANCES

When planning the installation, consider the location of the
vent terminal and clearances. Some of the most common
clearances to keep in mind are shown in Figure 11.
Important: All vent clearances must be maintained.
Check your vent termination clearances against Fig-
ures 11 and 12.
The vent should be placed so that people cannot be burned
by accidentally touching the vent surfaces when the stove
is operating.
The vent termination should be located where it cannot be
damaged by such things as automobile doors, lawn mowers
or snowblowers and it should be located away from areas
where it could become blocked by snow, etc.
Some considerations are:
• Obstructions or impediments to venting.
• Nearby combustible materials that could come into con-
tact with combustion exhaust gases.
• Other nearby openings {within 12" (305 mm)} through
which exhaust gas could reenter the building.
• All vegetation within 3' (76 mm) that may interfere with
the draft.
Other factors that influence where the installation will be
sited include the location of outside walls, where additional
heat may be desired in the home, where the family mem-
bers gather most regularly, and perhaps most importantly,
the distance limitations of the venting system.
IMPORTANT
The horizontal termination must not be recessed into
the exterior wall or siding.
Horizontal vent runs must be level toward the vent
termination.
Clearances around the vent termination must be
maintained.
For installations using DuraVent pipe, parallel instal-
lations with minimum wall clearance have restricted
access for connecting the Horizontal Vent Cap straps
to the vent pipe. See the maker's instructions for rec-
ommended installation procedures.
1010
Radiance
Your stove is approved to be vented either through the side
wall, or vertical through the roof.
• HHT does not require any opening for inspection of vent
pipe.
• Only HHT SLP venting components or DuraVent vent-
ing components specifically approved and labeled for
this stove may be used.
• Minimum clearances between vent pipes and combus-
tible materials is one (1") inch (25 mm), except where
stated otherwise.
• Venting terminals shall not be recessed into a wall or
siding.
• Horizontal venting must be installed on a level plane
without an inclining or declining slope.
There must not be any obstruction such as bushes, garden
sheds, fences, decks or utility buildings within 24" from the
front of the termination hood.
Do not locate termination hood where excessive snow or
ice build up may occur. Be sure to check vent termination
area after snow falls, and clear to prevent accidental block-
age of venting system. When using snow blowers, make
sure snow is not directed towards vent termination area.
LOCATION OF VENT TERMINATION
It is imperative the vent termination be located observing
the minimum clearances as shown in this manual.