Replace the d rain hose
Rear view for left piping installation
Drain cap
How to pull the piping and drain hose out, in case
of the embeddedpiping
Apply putty or
caulking material
to seal the wall
opening.
PVC tube for
drain hose (VP-20)
PVC tube
for drain
hose
11.2.4

Connect the Cable to the Indoor Unit

The power supply cord, indoor and outdoor unit connection cable can be connected without removing the front grille.
1
Install the indoor unit on the installing holder that mounted on the wall.
2
Open the front panel and grille door by loosening the screw.
3
Cable connection to the power supply through Isolating Devices (Disconnecting means).
Connect the approved polychloroprene sheathed power supply cord 3 × 1.5 mm
o
245 IEC 57 or heavier cord to the terminal board, and connect the other end of the cable to Isolating
Devices (Disconnecting means).
Do not use joint power supply cord. Replace the wire if the existing wire (from concealed wiring, or
o
otherwise) is too short.
In unavoidable case, joining of power supply cord between isolating devices and terminal board of air
o
conditioner shall be done by using approved socket and plug with earth pin rated 15/16A. Wiring work to
both socket and plug must follow to national wiring standard.
4
Bind all the power supply cord lead wire with tape and route the power supply cord via the left escapement.
5
Connection cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 ×
2
1.5 mm
flexible cord, type designation 245 IEC 57 or heavier cord. Do not use joint connection cable.
Replace the wire if the existing wire (from concealed wiring, or otherwise) is too short.
6
Bind all the indoor and outdoor connection cable with tape and route the connection cable via the right
escapement.
Drain hose
.
Connection
cable
Piping
PVC tube (VP-65) for piping
and connection cable
PVC tubefor drain hose (VP-30)
Cable
Piping
Indoor unit
72 mm
Piping
Drain hose
In case of left piping how to insert
the connection cable and drain hose.
Drain hose
from main unit
(For the right piping, follow the
same procedure)
29
Connection cable
More than 1150 mm
Sleeve for piping hole
Drain
hose
Cable
Piping
2
, type designation