Connect The Cable To The Indoor Unit - Panasonic CS-E9RKUAW Installation Manual

Indoor/outdoor unit
Hide thumbs Also See for CS-E9RKUAW:

Advertisement

Replace the drain hose
Rear view for left piping installation
Drain hose
Drain cap
How to pull the piping and drain hose out, in case of embedded piping.
Apply putty or
caulking material
to seal the wall
opening.
PVC tube for
drain hose (VP-20)
PVC tube
for drain
hose
9
Drain hose adapter
usage
Join indoor drain hose to 3/4" (20 mm) nominal PVC pipe size
by using drain hose adapter
Remarks :
Make sure indoor unit drain hose & 3/4" (20 mm) nominal PVC pipe
are fully inserted to drain hose adapter
11.2.4

Connect the Cable to the Indoor Unit

1. The inside and outside connection cable can
be connected without removing the front grille.
2. Unscrew the conduit cover and fix the conduit
connector to conduit cover with lock nut, then
secure it against chassis.
3. Connection cable between indoor unit and
outdoor unit should be UL listed or CSA
approved 4 conductor wires minimum AWG16
in accordance with local electric codes.
4. Connection cable between indoor unit and
outdoor unit should be UL listed or CSA
approved 4 conductor wires minimum AWG16
in accordance with local electric codes.
Ensure the colour of wires of outdoor unit
o
and terminal number are the same as the
indoor's repectively.
Terminals on the indoor unit
Colour of wires (connection cable)
Terminals on the outdoor unit
WARNING
This equipment must be properly earthed.
Drain hose
Connection
cable
Adjust the piping slightly downwards.
Connection
cable
Piping
Drain hose
from main unit
PVC tube (VP-65) for piping
and connection cable
PVC tube for drain hose (VP-30)
Cable
Piping
Indoor unit
3
15
/
" (100 mm)
16
9
when necessary.
9
.
1
2
3
1
2
3
Piping
Drain hose
Sleeve for piping hole
How to insert the connection cable and drain hose
in the case of left piping.
(For right piping, follow the same procedure)
Indoor unit
drain hose
3/4" (20 mm) nominal PVC pipe
- Install incline downward more than 1°
- Apply PVC glue at the join.
Earth lead wire shall be Yellow/Green
o
(Y/G) in colour and shall be longer than
other lead wires as shown in the figure for
electrical safety in case of the slipping.
Conduit
Connector
Lock Nut
Indoor and
outdoor
connection
cable
36
Connection
cable
More than 37
13
/
"
32
(950 mm)
Drain
hose
Cable
Piping
Close join by Vinyl Tape ( )
9
Drain hose adapter
Conduit
Cover
Chassis
Rear Side of Indoor Unit
Terminal
Board
1
2
3
Earth Wire
longer than
others AC
wires for
safety
reason
Holder