15.4.18 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry)
Error Code will not display (no Timer LED blinking) but store in EEPROM
Malfunction Decision Conditions
Freeze prevention control takes place (when indoor pipe temperature is lower than 2°C)
Malfunction Caused
Air short circuit at indoor unit
Clogged indoor unit air filter
Dust accumulation on the indoor unit heat exchanger
2/3 way valve closed
Faulty indoor unit fan motor
Refrigerant shortage (refrigerant leakage)
Clogged expansion valve or strainer
Faulty indoor pipe temperature sensor
Faulty indoor unit PCB
Troubleshooting
When abnormality indication starts again
Check the air passage
Is there any short circuit?
Check the indoor unit air filter
Is the air filter dirty?
Check the dust accumulation on the indoor unit heat exchanger
Is the indoor unit heat exchanger dirty?
Check if 2/3 way valve is closed?
Check if inddor fan motor operates normally?
Check for gas leakage. Is Oil oozing out from the 2/3 way valve?
Check if expansion valve or strainer clogged (ice formed)?
Check the indoor pipe temperature sensor
Does it conform to the sensor characteristic chart?
NO
NO
NO
YES
NO
YES
69
For safety reason and to prevent
component breakdown, always switch
off the power before remove and
connect the component.
YES
Provide sufficient air passage
YES
Clean the air filter
YES
Clean the indoor unit heat exchanger
YES
Open the 2/3 way valve
NO
Replace the indoor unit fan motor and/or
indoor unit PCB
YES
Repair the pipe flare or union nuts
Reclaim and recharge refrigerant
YES
Reclaim and recharge with correct amount
of refrigerant
NO
Replace the indoor pipe temperature
sensor
Replace the indoor unit PCB