Field Adjustable Trip Points - Fronius IG Plus 3.0-1 Operating Instructions Manual

For grid-connected photo-voltaic systems
Table of Contents

Advertisement

Field adjustab-

Field adjustable trip points

le trip points
Nominal AC output voltage,
Line-to-Line, [V]
Operating AC voltage range
default, Line-to-Line, [V]
Adjustment range for
voltage, Line-to-Line, [V]
Voltage trip limit accuracy,
Line-to-Line [% of nominal value]
Operating AC voltage range,
Line-to-Neutral, [V]
Adjustment range for voltage,
Line-to-Neutral, [V]
Adjustment range for voltage
clearing time [s]
Voltage trip limit accuracy,
Line-to-Neutral [% of nominal value]
Nominal output frequency [Hz]
Operating frequency
range [Hz]
Adjustment range for
frequency [Hz]
Adjustment range for frequency
clearing time [s]
Frequency trip limit accuracy [ms] 16.66
Detection time [ms]
Reconnect time default [s]
Adjustment range for reconnect
time [s]
(1)
(2)
16.66 ms are equivalent to 1 cycle
25 ms are equivalent to 1.5 cycles
208 V
208
183-229
105-248
1
106-132
61-143
0.016-4.25
1
60
59.3-60.5
57.0-60.48
0.016-300
(1)
(2)
25
300
5-900
159
240 V
277 V
240
277
211-264
-
121-287
-
1
-
106-132
244-305
61-143
138-324
0.016-4.25
0.016-4.25
1
1
60
60
59.3-60.5
59.3-60.5
57.0-60.48
57.0-60.48
0.016-300
0.016-300
(1)
(1)
16.66
16.66
(2)
(2)
25
25
300
300
5-900
5-900