Viessmann Vitodens 333 Service Instructions Manual page 57

Compact gas fired condensing boiler
Hide thumbs Also See for Vitodens 333:
Table of Contents

Advertisement

Code 2
(cont.)
Coding in the delivered condition
E9:45
Speed of the external
variable speed heating
circuit pump: 45 % of
the maximum speed in
reduced temperature
mode (only for weather-
compensated control
units)
F2:8
Time limit for party
mode 8 h or external
heating program chan-
geover via the keyboard
(only for weather-com-
pensated control units)
*
1
F5:12
Run-on time of the inter-
nal circulation pump in
heating mode (only for
constant temperature
control units)
F6:25
In the "DHW only" oper-
ating mode, the internal
circulation pump is per-
manently ON (only for
weather-compensated
control units)
F7:25
In the "Standby" operat-
ing mode, the internal
circulation pump is per-
manently ON (only for
constant temperature
control units)
Party mode ends automatically in the "Heating and DHW" program, when the system
*1
changes over to operation with standard room temperature.
Possible change
E9:0
Speed adjustable from 0
to
to 100 % of maximum
E9:100
speed during operation
with reduced room tem-
perature
F2:0
No time limit for party
*
1
mode
F2:1
Time limit adjustable from
to
1 to 12 h
F2:12
F5:0
No run-on time of the in-
ternal circulation pump
F5:1
Run-on time of the inter-
to
nal circulation pump ad-
F5:20
justable from 1 to 20 min
F6:0
In the "DHW only" operat-
ing mode, the internal cir-
culation pump is
permanently OFF
F6:1
In the "DHW only" operat-
to
ing mode, the internal cir-
F6:24
culation pump will be
started 1 to 24 times per
day for 10 min respec-
tively.
F7:0
In "Standby mode", the
internal circulation pump
is permanently OFF
F7:1
In the "Standby" mode,
to
the internal circulation
F7:24
pump in operating mode
will be started 1 to 24
times per day for 10 min
respectively.
Coding
*
1
57