Viessmann Vitodens 333 Service Instructions Manual page 36

Compact gas fired condensing boiler
Hide thumbs Also See for Vitodens 333:
Table of Contents

Advertisement

Initial start-up, inspection, maintenance
Further details regarding the individual steps
Updating the LON user list
Note
Only possible if all users are connected and the control unit is programmed to
be fault manager (code "79:1").
Press the following keys:
1. L + d simultaneously for
approx. 2 s
User check initiated (see
page 37).
Single boiler system with Vitotronic 050 and Vitocom 300
Note
In each heating system, only one Vitotronic may be programmed as fault man-
ager.
Boiler control
Vitotronic 050
unit
User no. 1
User no. 10
Code "77: 1"
Set code "77: 10"
Control unit is
Control unit is not
fault manager
fault manager
Set code "79: 1"
Code "79: 0"
Send time via
Time received via
LON
LON
Code "7b: 1"
Set code "81: 3"
Transmit outside
The outside tem-
temperature via
perature is re-
LON
ceived via LON
Set code "97: 2"
Set code "97: 1"
Fault monitoring
Fault monitoring
LON user code
LON user code
"9C:20"
"9C:20"
36
(cont.)
2. e
The user list is updated
after approx. 2 min.
The user check is com-
pleted.
Vitotronic 050
User no. 11
Set code "77: 11"
Control unit is not
fault manager
Code "79: 0"
Time received via
LON
Set code "81: 3"
The outside tem-
perature is received
via LON
Set code "97: 1"
Fault monitoring
LON user code
"9C:20"
Vitocom
User no. 99
Control unit is
fault manager
Time received
via LON