Viessmann Vitodens 333 Service Instructions Manual page 14

Compact gas fired condensing boiler
Hide thumbs Also See for Vitodens 333:
Table of Contents

Advertisement

Initial start-up, inspection, maintenance
Further details regarding the individual steps
1. Close the gas shut-off valve.
2. Release screw A inside test nip-
ple "PE" on the gas combination
valve, but do not remove it; then
connect the pressure gauge.
3. Open the gas shut-off valve.
Supply (flow)
Supply (flow)
pressure for nat-
pressure for
ural gas
LPG (only 26 kW)
below 17.4 mbar
below 42.5 mbar
17.4 to 57.5 mbar
42.5 to 57.5 mbar
in excess of
in excess of
57.5 mbar
57.5 mbar
14
(cont.)
4. Record the static pressure and
record it in the service report on
page 117.
Set value: max. 57.5 mbar
5. Start up the boiler.
Note
During commissioning, the boiler
can enter a fault state because of
airlocks in the gas pipe. After
approx. 5 s press "E" to reset the
burner.
6. Check the supply (flow) pressure.
Set value:
&
Natural gas: 20 mbar
&
LPG (only 26 kW): 50 mbar
Note
Use suitable test equipment, with a
resolution of at least 0.1 mbar, to
measure the supply pressure.
7. Record the actual value in the ser-
vice report on page 117.
Take the action shown in the table.
Measures
Never start up. Notify your mains gas
or LPG supplier.
Start up the boiler.
Install a separate gas governor down-
stream of the system and regulate the
inlet pressure to 20 mbar for natural
gas or 50 mbar for LPG. Notify your
mains gas or LPG supplier.