Du/dt fillter plus voltage peak limiter
Hide thumbs Also See for SINAMICS G120P:

Advertisement

Components
The order numbers of the individual components (du/dt reactor and voltage peak limiter) are
listed in the following table:
Table 2- 2
du/dt filter plus Voltage Peak Limiter, order numbers of the individual components
du/dt filter plus Voltage Peak Limiter
6SL3000-2DE35-0AA0
6SL3000-2DE38-4AA0
Limiting the rate of voltage rise and the voltage peaks using an output reactor and du/dt filter plus
Voltage Peak Limiter
Fast-switching IGBTs in the converter result in high voltage gradients du/dt at the converter
output. If long motor cables are used, this leads to an additional current load on the
converter due to capacitive charge/discharge currents. The high voltage gradients, and the
resulting transients at the motor terminals, cause the motors' electrical winding load to
increase as compared with direct on-line operation.
The du/dt filter plus Voltage Peak Limiter limits the rate of voltage rise to values < 500 V/µs
and the typical voltage peaks Û
150 m)
dV/dt filter plus Voltage Peak Limiter
Operating Instructions, 04/2014, A5E32847105B AB
du/dt reactor
Line voltage 380 V – 480 V 3 AC
6SL3000-2DE35-0CA0
6SL3000-2DE38-4CA0
to < 1000 V at U
LL
Voltage limiting network
6SL3000-2DE35-0BA0
6SL3000-2DE38-4BA0
≤ 575 V (for motor cable lengths of ≤
line
General