Cooling Operation - Fujitsu ARU9RLF Service Instruction

Slim duct type inverter
Hide thumbs Also See for ARU9RLF:
Table of Contents

Advertisement

1. COOLING OPERATION

A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is 4°F(2°C) higher than a set temperature, the compressor operation
frequency will attain to maximum performance.
* If the room temperature is 5°F(2.5°C) lower than a set temperature, the compressor will be
stopped.
* When the room temperature is between +4°F(+2°C) to -5°F(-2.5°C) of the setting temperature,
the compressor frequency is controlled within the range shown in Table 1.
However, the maximum frequency is limited in the range shown in Fig. 1 based on the
fan speed mode and the outdoor temperature.
( Table 1 : Compressor frequency range )
AOU9RLFC
AOU12RLFC
AOU18RLFC
When the compressor operates for 30 minutes continuously at over the maximum frequency ,
the maximum frequency is changed from Maximum Frequency
( Fig. 1 : Outdoor temperature zone )
Outside air
temperature
A zone
93°F
(34°C)
B zone
86°F
(30°C)
C zone
66°F
(19°C)
D zone
50°F
(10°C)
E zone
32°F
(0°C)
F zone
Minimum
Maximum
frequency
frequency
10rps
74rps
74rps
10rps
104rps
12rps
Outside air
temperature
97°F
(36°C)
90°F
(32°C)
70°F
(21°C)
54°F
(12°C)
36°F
(2°C)
Maximum
frequency
57rps
57rps
68rps
to Maximum Frequency .
( Table 2 : Limit of maximum speed based on outdoor temperature )
Outdoor
temp. zone
AOU9RLFC
A zone
B zone
C zone
D zone
E zone
F zone
AOU12RLFC
A zone
B zone
C zone
D zone
E zone
F zone
AOU18RLFC
A zone
B zone
C zone
D zone
E zone
F zone
01-01
Indoor fan mode
Hi
Me
Lo
Quiet
74rps
49rps
44rps
35rps
74rps
49rps
44rps
35rps
74rps
49rps
44rps
35rps
49rps
40rps
31rps
22rps
49rps
40rps
31rps
22rps
49rps
40rps
31rps
22rps
74rps
49rps
44rps
35rps
74rps
49rps
44rps
35rps
74rps
49rps
44rps
35rps
49rps
40rps
31rps
22rps
49rps
40rps
31rps
22rps
49rps
40rps
31rps
22rps
104rps
59rps
48rps
30rps
104rps
59rps
48rps
30rps
72rps
48rps
41rps
30rps
48rps
41rps
34rps
21rps
48rps
41rps
34rps
21rps
48rps
41rps
34rps
21rps