Fujitsu ARU9RLF Service Instruction page 38

Slim duct type inverter
Hide thumbs Also See for ARU9RLF:
Table of Contents

Advertisement

For AOU9 / 12RLFC
Trouble shooting 10-1
OUTDOOR UNIT Error Method:
INDOOR UNIT
PFC circuit error
Detective Actuators:
Outdoor unit Main PCB
Forecast of Cause :
1. External cause
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current
Noise : Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OK
OK
Check Point 2 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 3 : Replace Main PCB
If Check Point 1, 2 do not improve the symptom, change Main PCB.
Indicate or Display:
Refer to error code table.
Detective details:
When inverter output DC voltage is higher than 415V for over 3 seconds,
the compressor stops.
If the same operation is repeated 5 times, the compressor stops permanently.
2. Connector connection failure
in the power supply circuit.
3. Main PCB failure
02-13