Fujitsu ARU9RLF Service Instruction page 57

Slim duct type inverter
Hide thumbs Also See for ARU9RLF:
Table of Contents

Advertisement

SERVICE PARTS INFORMATION 3
Outdoor unit Electronic Expansion Valve
( EEV )
Check Point 1 : Check Connections
Check connection of connector (CN40 or CN700)
( Loose connector or open cable )
EXPANSION
CN40
VALVE COIL
RED
[9/12RLFC]
1
1
BLUE
2
2
ORANGE
3
3
YELLOW
CN700
4
4
WHITE
5
5
[18RLFC]
Check Point 2 : Check Coil of EEV
Remove connector, check each winding
resistance of Coil.
Read wire
White - Red
Yellow - Red
Orange - Red
Blue - Red
If Resistance value is abnormal, replace EEV.
Check Point 5 : Check Opening and Closing Operation of Valve
When Valve is closed,
it has a temp. difference between Inlet and Outlet.
CLOSE
Example : Hot Gas
Pipe (In)
Hi TEMP.
Check Point 6 : Check Strainer
Strainer normally does not have temperature difference between inlet and outlet as shown in
but if there is a difference as shown in
Pipe (In)
EV
Resistance value
46
4
at 68°F(20°C)
Pipe (Out)
Normal TEMP.
, there is a possibility of inside clogged. In this case, replace Strainer.
Pipe (Out)
Check Point 3 : Check Voltage from Main PCB.
Remove Connector and check Voltage (DC12V)
If it does not appear, replace Main PCB.
Check Point 4 : Check Noise at start up
Turn on Power and check operation noise.
If an abnormal noise does not show,
replace Main PCB.
If it is open,
it has no temp. difference between Inlet and Outlet.
OPEN
Example : Hot Gas
Pipe (In)
Hi TEMP.
Pipe (In)
02-32
DC
Pipe (Out)
Hi TEMP.
,
Pipe (Out)