Defrost Operation Control - Fujitsu ARU9RLF Service Instruction

Slim duct type inverter
Hide thumbs Also See for ARU9RLF:
Table of Contents

Advertisement

21. DEFROST OPERATION CONTROL

1. CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts as shown in the following Table 19.
(Table 19 : Condition of starting Defrost Operation)
Normal defrost
Integrating defrost
If the compressor continuous operation time is less than 10 minutes,
the OFF number of the compressor is counted.
If any defrost operated, the compressor OFF count is cleared.
2. CONDITION OF THE DEFROST OPERATION COMPLETION
Defrost operation is released when the conditions become as shown in Table 20.
(Table 20 : Defrost Release Condition)
Outdoor heat exchanger temperature sensor value is higher than
+16°C(60.8°F) or Compressor operation time has passed 15 minutes.
Less than 25 minutes (
9/ 12RLFC
Less than 40 minutes (
18RLFC
Does not operate
More than 240 minutes
(For continuous operation)
Outdoor heat exchanger
temperature below 26.6°F(-3°C)
Release Condition
Compressor integrating operation time
)
More than 25 minutes (
)
More than 40 minutes (
Outdoor heat exchanger temp. < 1.4°F(-17°C)
(at outside air temp. > 14°F(-10°C))
=
Outdoor heat exchanger temp. < Outside air temp.-(12.6°F (7°C))
or Outdoor heat exchanger temp.< -13°F (-25°C)
(at -4°F (-20°C)< Outside air temp.< 14°F (-10°C))
=
Outdoor heat exchanger temp. < Outside air temp.-(12.6°F (7°C))
or Outdoor heat exchanger temp. < -22°F(- 30°C)
(at outside air temp. < -4°F(-20°C))
=
Compressor integrating operation time
More than 213 minutes
(For continuous operation)
Outdoor heat exchanger
temperature below 23°F(-5°C)
01-16
)
9/ 12RLFC
)
18RLFC
=
=
=
=
Less than 10 minutes
( For intermittent operation )
OFF count of the compressor
40 times

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aru18rlfAru12rlfAou9rlfcAou12rlfcaou18rlfc

Table of Contents