Cooling Operation - Fujitsu AS G09LMCB Series Service Instruction

Table of Contents

Advertisement

1. COOLING OPERATION

A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is
frequency will attain to maximum performance.
* If the room temperature is some degrees lower than a set temperature,
the compressor will be stopped.
* When the room temperature is between
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Fig.1 based on the indoor
fan mode and the outdoor temperature.
( Table 1 : Compressor frequency range )
AO*G09LMCBN
AO*G12LMCBN
AO*G14LMCBN
( Fig.1 : Outdoor temperature zone )
Outdoor
temperature drops
A zone
34°C
B zone
30°C
C zone
19°C
D zone
10°C
E zone
0°C
F zone
2°C
higher than a set temperature, the compressor operation
+2°C
to
Minimum
Maximum
frequency
frequency
18rps
64rps
18rps
96rps
10rps
80rps
( Table 2 : Limit of maximum speed based on outdoor temperature )
Outdoor
temperature rises
36°C
32°C
21°C
12°C
2°C
-2.5°C
of the setting temperature,
Outdoor
temp. zone
A zone
AO*G09LMCBN
B zone
C zone
D zone
E zone
F zone
AO*G12LMCBN
A zone
B zone
C zone
D zone
E zone
F zone
AO*G14LMCBN
A zone
B zone
C zone
D zone
E zone
F zone
01-01
Indoor fan mode
Hi
Me
Lo
Quiet
64rps
50rps
42rps
30rps
64rps
50rps
42rps
30rps
64rps
50rps
42rps
30rps
52rps
45rps
40rps
29rps
52rps
45rps
40rps
29rps
52rps
45rps
40rps
29rps
96rps
61rps
51rps
33rps
96rps
61rps
51rps
33rps
96rps
61rps
51rps
33rps
68rps
48rps
36rps
27rps
68rps
48rps
36rps
27rps
68rps
48rps
36rps
27rps
80rps
51rps
43rps
26rps
80rps
51rps
43rps
26rps
80rps
51rps
43rps
26rps
59rps
40rps
29rps
20rps
59rps
40rps
29rps
20rps
59rps
40rps
29rps
20rps