Cooling Operation - Fujitsu ASYG09LLCB Service Instruction

Split type room air conditioner wall mounted type inverter, refrigerant r410a, indoor/outdoor unit
Table of Contents

Advertisement

1. COOLING OPERATION

A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is 2°C higher than a set temperature, the compressor operation
frequency will attain to maximum performance.
* If the room temperature is some degrees lower than a set temperature,
the compressor will be stopped.
* When the room temperature is between +2°C to -2.5°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Fig.1 based on the indoor
fan mode and the outdoor temperature.
( Table 1 : Compressor frequency range )
Minimum
Model
frequency
07/09
18rps
12
16rps
( Fig.1 : Outdoor temperature zone )
When the outdoor
temperature drops
A zone
34°C
B zone
30°C
C zone
19°C
D zone
10°C
E zone
0°C
F zone
Maximum
frequency
64rps
87rps
( Table 2 : Limit of maximum speed based on outdoor temperature )
When the outdoor
temperature rises
36°C
32°C
21°C
12°C
2°C
01-01
Outdoor
Model
temp. zone
A zone
07, 09
B zone
C zone
D zone
E zone
F zone
A zone
12
B zone
C zone
D zone
E zone
F zone
Indoor fan mode
Hi
Me
Lo
Quiet
64rps
51rps
42rps
30rps
64rps
51rps
42rps
30rps
64rps
51rps
42rps
30rps
48rps
45rps
39rps
30rps
48rps
45rps
39rps
30rps
48rps
45rps
39rps
30rps
87rps
55rps
46rps
30rps
87rps
55rps
46rps
30rps
87rps
55rps
46rps
30rps
62rps
52rps
44rps
30rps
62rps
52rps
44rps
30rps
62rps
52rps
44rps
30rps