Function Setting; Indoor Unit - Fujitsu ARU9RLF Service Instruction

Slim duct type inverter
Hide thumbs Also See for ARU9RLF:
Table of Contents

Advertisement

3-1. FUNCTION SETTING

3-1-1 INDOOR UNIT

Follow the instructions in the Local Setup Procedure, which is supplied with the remote control,
in accordance with the installed condition.
After the power is turned on, perform the Function Setting on the remote control.
The settings may be selected between the following two: Function Number or Setting Value.
Settings will not be changed if invalid numbers or setting values are selected.
1-1. Setting the Filter sign
The indoor unit has a sign to inform the user that it is time to clean the filter.
Select the time setting for the filter sign display interval in the table below according to
the amount of dust or debris in the room.
If you do not wish the filter sign to be displayed, select the setting value for "No indication".
Setting Description
Standard
Long interval
Short interval
No indication
1-2. Setting the Static pressure
Select appropriate static pressure according to the installation conditions.
Setting Description
0 Pa
10 Pa
20 Pa
30 Pa
40 Pa
50 Pa
60 Pa
70 Pa
80 Pa
90 Pa
25 Pa [Standard]
(
Factory setting)
Function Number
Setting Value
11
(
Factory setting)
Function Number
Setting Value
26
03-01
00
01
02
03
00
01
02
03
04
05
06
07
08
09
31