Fujitsu ARU9RLF Service Instruction page 41

Slim duct type inverter
Hide thumbs Also See for ARU9RLF:
Table of Contents

Advertisement

Trouble shooting 12
OUTDOOR UNIT Error Method:
INDOOR UNIT
Discharge thermistor error
Detective Actuators:
Outdoor unit Main PCB
Discharge pipe temperature thermistor
Forecast of Cause :
1. Connector connection failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 2 :
Thermistor Characteristics (Approx. value)
Temperature (°F)
Resistance Value (k )
Temperature (°F)
Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Check Point 3 :
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
AOU9 / 12RLFC
THERMISTOR
(PIPE)
BLACK
BLACK
BROWN
BROWN
THERMISTOR
(DISCHARGE)
THERMISTOR
(OUTDOOR)
BLACK
BLACK
If the voltage does not appear, replace Main PCB.
Indicate or Display:
Refer to error code table.
Detective details:
When Discharge pipe temperature thermistor open or short-circuit
is detected at power ON or while running the compressor.
2.Thermistor failure
14°F
23°F
32°F
41°F
292.9
221.1
168.6
129.8
140°F
158°F
176°F
194°F
12.3
8.7
6.3
AOU18RLFC
THERMISTOR
(PIPE)
1
1
2
2
CN71
3
3
4
4
THERMISTOR
(DISCHARGE)
THERMISTOR
(OUTDOOR)
1
1
CN70
2
2
3
3
3. Main PCB failure
50°F
68°F
86°F
40.0
100.9
62.5
212°F
230°F
248°F
4.6
3.4
2.6
2.0
BLACK
1
1
BLACK
2
2
BLACK
3
3
BLACK
4
4
BLACK
1
1
2
2
BLACK
3
3
02-16
104°F
122°F
26.3
17.8
CN61
CN62

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aru18rlfAru12rlfAou9rlfcAou12rlfcaou18rlfc

Table of Contents