Flue System - AGA DC3G Installation Manual

Dual control
Hide thumbs Also See for DC3G:
Table of Contents

Advertisement

SEE FIGS. 5, 6, 7, 8 & 9
The flue system must be installed in accordance with the federal, state and local codes.
Only genuine AGA approved flue pipe is to be used.
Maximum permitted flue length run including bends is 13 ft.
Products of combustion discharge is by a fan powered flue pipe of 2" (50mm) diameter which can reach up
to 13' (4 metres) in length through a maximum of 4 x 90° bend. Exits from the appliance can be from rear, LH
or RH sides. (See Figs. 6 and 7).
The flue pipe should protrude through the outside wall fixing plate by 1" (25mm) (See Fig. 5).
Terminal Position
The minimum acceptable spacings from the terminal to obstructions and ventilation openings are as shown
in Fig. 7.
Where the terminal is fitted within 23
(1000mm)
long should be fitted to the underside and immediately beneath the guttering or eaves.
Where the terminal is fitted within 17
1
/
(750mm) long should be fitted to the underside and immediately beneath the guttering or eaves.
2
Terminal Protection
A terminal guard is supplied with the range and must be fitted, if flue termination is less than 78
metres) above ground level, or subject to damage.
When fitted, it must be positioned to provide a minimum of 2" (50mm) clearance from any part of the terminal
and be central over the terminal.
EXTERNAL
WALL
Fig. 5

FLUE SYSTEM

5
/
" (600mm) below plastic guttering an aluminium shield 39
8
3
/
" (450mm) below eaves or painted guttering an aluminium shield 29
4
(38mm)
1"
(25mm)
Fig. 6
NOTE: A 5" hole clearance is required through
combustible material, to allow 1 1/2" clearance
around flue pipe, (See Fig. 6).
DESN 511196
12
1
1
/
"
2
VENT PIPE
3
/
"
8
3
/
" (2
4
COMBUSTIBLE
WALL
DESN 517038