Gas Piping Connections - Goodman GMVC950704CX Installation Instructions Manual

Hide thumbs Also See for GMVC950704CX:
Table of Contents

Advertisement

Contact your distributor for a tabular listing of appropriate
manufacturer's kits for propane gas and/or high altitude installa-
tions. The indicated kits must be used to insure safe and proper
furnace operation. All conversions must be performed by a quali-
fied installer, or service agency.
G
V
AS
ALVE
This unit is equipped with a 24 volt gas valve controlled during
furnace operation by the integrated control module. As shipped,
the valve is configured for natural gas. The valve is field convertible
for use with propane gas by replacing the regulator spring with a
propane gas spring from an appropriate manufacturer's propane
gas conversion kit. Taps for measuring the gas supply pressure
and manifold pressure are provided on the valve.
The gas valve has a manual ON/OFF control located on the valve
itself. This control may be set only to the "ON" or "OFF" position.
Refer to the lighting instructions label or Startup Procedure &
Adjustment for use of this control during start up and shut down
periods.
G
P
C
AS
IPING
ONNECTIONS
T
 
 
 
O
AVOID
POSSIBLE
UNSATISFACTORY
 
 
 
DAMAGE
DUE
TO
UNDERFIRING
 
/
 
 
OF
NATURAL
PROPANE
GAS
PIPING
 
/
 
 
 
THE
METER
TANK
TO
THE
FURNACE
When sizing a trunk line, be sure to include all appliances which
will operate simultaneously when sizing a trunk line.
The gas piping supplying the furnace must be properly sized based
on the gas flow required, specific gravity of the gas, and length of
the run. The gas line installation must comply with local codes, or
in their absence, with the latest edition of the National Fuel Gas
Code, NFPA 54/ANSI Z223.1.
Natural Gas Capacity of Pipe
In Cubic Feet of Gas Per Hour (CFH)
Length of
Pipe in Feet
1/2"
3/4"
10
132
20
92
30
73
40
63
50
56
60
50
70
46
80
43
90
40
100
38
(Pressure 0.5 psig or less and pressure drop of 0.3" W.C.; Based on
0.60 Specific Gravity Gas)
CFH = BTUH Furnace Input
Heating Value of Gas (BTU/Cubic Foot)
To connect the furnace to the building's gas piping, the installer
must supply a ground joint union, drip leg, manual shutoff valve,
and line and fittings to connect to gas valve. In some cases, the
WARNING
 
 
 
OPERATION
OF
EQUIPMENT
 
 
 
 
OR
EQUIPMENT
USE
THE
PROPER
 
 
 
 
NEEDED
WHEN
RUNNING
PIPE
.
Nominal Black Pipe Size
1"
1 1/4"
278
520
1050
190
350
730
152
285
590
130
245
500
115
215
440
105
195
400
96
180
370
90
170
350
84
160
320
79
150
305
installer may also need to supply a transition piece from 1/2" pipe
to a larger pipe size.
The following stipulations apply when connecting gas piping. Re-
fer to Gas Piping Connections figure for typical gas line connec-
tions to the furnace.
Use black iron or steel pipe and fittings for building piping.
Where possible, use new pipe that is properly chamfered,
reamed, and free of burrs and chips. If old pipe is used, be
sure it is clean and free of rust, scale, burrs, chips, and old
pipe joint compound.
Use pipe joint compound on male threads ONLY. Always
use pipe joint compound (pipe dope) that is APPROVED
FOR ALL GASSES. DO NOT apply compound to the first
two threads.
Use ground joint unions.
Install a drip leg to trap dirt and moisture before it can enter
the gas valve. The drip leg must be a minimum of three
inches long.
Install a 1/8" NPT pipe plug fitting, accessible for test gage
connection, immediately upstream of the gas supply
connection to the furnace.
Always use a back-up wrench when making the connection
 
to the gas valve to keep it from turning. The orientation of
 
 
SIZE
the gas valve on the manifold must be maintained as shipped
 
 
FROM
from the factory. Maximum torque for the gas valve
connection is 375 in-lbs; excessive over-tightening may
damage the gas valve.
Install a manual shutoff valve between the gas meter and
unit within six feet of the unit. If a union is installed, the
union must be downstream of the manual shutoff valve,
between the shutoff valve and the furnace.
Tighten all joints securely.
Connect the furnace to the building piping by one of the
following methods:
Rigid metallic pipe and fittings.
1 1/2"
Semi-rigid metallic tubing and metallic fittings.
1600
Aluminum alloy tubing must not be used in exterior
1100
locations. In order to seal the grommet cabinet
980
penetration, rigid pipe must be used to reach the outside
760
670
of the cabinet. A semi-rigid connector to the gas piping
610
may be used from there.
560
530
Use listed gas appliance connectors in accordance with
490
their instructions. Connectors must be fully in the same
460
room as the furnace.
Protect connectors and semirigid tubing against physical
and thermal damage when installed. Ensure aluminum-
alloy tubing and connectors are coated to protect against
external corrosion when in contact with masonry, plaster,
or insulation, or subjected to repeated wetting by liquids
such as water (except rain water), detergents, or sewage.
31
G
S
AS
UPPLY AND
P
IPING

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents