Securing The Flue Pipe Sections (Dvp And Slp Pipe) - Heat & Glo SL-350TRS-CE-D Installer's Manual

Hide thumbs Also See for SL-350TRS-CE-D:
Table of Contents

Advertisement

H. Securing the Flue Pipe Sections (DVP and
SLP Pipe)
• Vertical runs of DVP pipe must be supported every 2.44
m after the 7.62 m maximum unsupported rise.
• Vertical runs of SLP pipe must be supported every 2.44 m.
• Horizontal sections must be supported every 1.52 m.
• Flue pipe supports or plumbers strap (spaced 120º apart)
may be used to support. See figures 40 and 41.
• Wall shield firestops may be used to provide horizontal
support.
• SLP ceiling firestops have tabs that may be used to
provide vertical support.
warNiNG! risk of fire, explosion or asphyxiation!
Improper support may allow flue pipe to sag and sepa-
rate. Use flue pipe run supports and connect flue pipe
sections per installation instructions. DO NOT allow flue
pipe to sag below connection point to appliance.
Figure 40 Securing vertical Pipe Sections
Figure 41 Securing Horizontal Pipe Sections
27
Heat & Glo • SL-350TRS-CE-D • 2033-900 Rev. V • 3/13